24 FLEX I/O 8 Input HART Analog Module
Publication
1794-IN108D-EN-P - January 2014
Configuration Map (Series A Mode)
Word Bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 Reserved High and Low Error
Level 0.
..3
u/d
0...3
Filter Cutoff
0...3
Data Format 0...3 FM
0...3
1 Sq. Root
Thresh.
High and Low Error
Level 4...7
u/d
4...7
Filter Cutoff
4...7
Data Format 4...7 FM
4...7
Where: u/d = remote transmitter error up/down
FM = fault mode
Sq. Root Thresh. = square root threshold
Fault Mode (Series A Mode)
Word 0 Bit 00 Fault enable for Channels 0...3
Word 1 Bit 00 Fault enable for Channels 4...7
Where: O = disable
1 = enable with wire-off overload
Filter Cutoff Selections (Series A Mode)
Word Bits Description
0 07 06 05 Channels 0...3
1 07 06 05 Channels 4...7
000Reserved
001Reserved
010Reserved
01110 Hz (100 ms)
1004 Hz (250 ms)
1012 Hz (500 ms)
1101 Hz (1 s)
1110.5 Hz (2 s)
Vue de la page 23