4 FLEX Integra 16 Source Input Module
Publication 1793-5.10 - December 1999
Wiring
This module is available with 2 styles of terminations: 1793-IV16 -
screw-cage and 1793-IV16S - spring-clamp. Refer to the wiring figure
below.
1. Connect individual sensor signal input leads to terminals 0 through 15
on row A (channels 0 thru 15 respectively).
2. Connect the associated sensor common lead to a COM terminal on
row (B).
3. Connect +24V dc voltage to V terminal on row B.
4. Connect 24V dc common to terminal COM on row A.
5. If daisy-chaining +24V dc from this module to the next Integra
module, connect a jumper from terminal V to terminal 8 on the next 8
point Integra module or terminal V on the next 16 point Integra
module.
6. If daisy-chaining 24V dc common from this module to the next FLEX
Integra module, connect a jumper from terminal COM on this module
to terminal 0 on the next 8 point Integra module, or to terminal COM
on the next 16 point Integra module.
.
!
ATTENTION: Total current draw through the module’s
(V) voltage terminals is limited to 10A. Separate power
connections to the module may be required.
0 12345 6789101112131415
A
B
41815
VV
COM
COM
COM
COM
1793-IV16S
A
B
01 23 45678 9101112131415COM
COM
VVCOM COM
41817
1793-IV16
Where: COM = common, V = +24V dc power, 0 thru 15 = inputs