10 FLEX Integra 16 Source Input Module
Publication 1793-5.10 - December 1999
Derating Curve
Conductors Wire Size
Category
12 gauge to 18 gauge (4mm
2
to 0.75mm
2
)
stranded wire rated @ 75
o
C minimum
3/64 in (1.2mm) maximum insulation
2
1
Screw Terminal Torque 5-7 lb-in (0.5-0.6Nm)
Agency Certification
(when product is marked)
C-UL Listed
C-UL Class I, Division 2 Groups A, B, C and D certified
UL listed
CE marked for all applicable directives
C-Tick marked for all applicable acts
1Use this category information for planning conductor routing as described in publication 1770-4.1, “Wiring and
Grounding Guidelines for Noise Immunity.”
Specifications - 16 Input Module Cat. No. 1793-IV16 and -IV16S
31.2
30
25
20
15
10
0
10 20 30 40 50 55 6037
27.5
Vin
On-State
Voltage
(V dc)
Ambient Temperature (
o
C)
41820