Rockwell-automation 1791-XXXX Discrete I/O AC and DC Block I/O Input a Manuel d'utilisateur Page 57

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 98
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 56
Installing Block I/O
Chapter 3
3-38
Certain products are not compatible with extended node capabilities
obtained with the use of 82 ohm terminators. Table 3.D lists those products
that are not compatible.
Table 3.D
Noncompatible
Products
Device Series
Scanners
1771SN All
1772SD All
1772SD2 All
1775SR All
1775S4A All
1775S4B All
Adapters  1771AS All
1771ASB Series A
1771DCM All
Miscellaneous  1771AF All
1771AF1 All
The remote I/O link can operate at three speeds: 57.6K, 115.2K or 230.4K
bits/s. The selection of link speed is dependent on the scanner/processor
used, throughput requirements, distance required and the type of remote
I/O devices being used.
Throughput Requirements
The throughput, a portion of which is I/O scan time, must be balanced
against the distance requirements for the application. The typical discrete
I/O scan time is shown in Table 3.E below. Use these values along with
your processor/scanner manual to determine system throughput.
Table 3.E
I/O
Scan Time vs. Remote I/O Link Distance
57.6K Bits/s 115.2K Bits/s 230.4K Bits/s
Typical Discrete I/O Scan
Time (each block)
10ms 7.0ms 3ms
Remote I/O link distance 10,000 ft. 5,000 ft. 2,500 ft.
Compatibility
of 1771 I/O
Products with Extended
Node Numbers
Selecting Remote I/O Link
Speed
Vue de la page 56
1 2 ... 52 53 54 55 56 57 58 59 60 61 62 ... 97 98

Commentaires sur ces manuels

Pas de commentaire