Publication 1771-IN038B-EN-P - August 2002
Contact Output Module
(Catalog Number 1771–OWNA)
Use this document as a guide when installing the catalog number
1771-OWNA series B contact output module.
To See page
Important User Information 1
Preinstallation Considerations 4
Power Supply Requirements 4
Key the Backplane Connector 5
Install the Module and Field Wiring Arm 6
Connect Wiring to the Field Wiring Arm 7
For this reference information See page
Interpreting the Status Indicators 11
Hazardous Location Approval 12
Specifications 13
Because of the variety of uses for the products described in this
publication, those responsible for the application and use of these
products must satisfy themselves that all necessary steps have been
taken to assure that each application and use meets all performance
and safety requirements, including any applicable laws, regulations,
codes and standards. In no event will Rockwell Automation be
responsible or liable for indirect or consequential damage resulting
from the use or application of these products.
Any illustrations, charts, sample programs, and layout examples
shown in this publication are intended solely for purposes of
example. Since there are many variables and requirements associated
with any particular installation, Rockwell Automation does not
assume responsibility or liability (to include intellectual property
liability) for actual use based upon the examples shown in this
publication.
Allen–Bradley publication SGI–1.1, Safety Guidelines for
Application, Installation, and Maintenance of Solid–State Control
(available from your local Rockwell Automation office), describes
some important differences between solid–state equipment and
electromechanical devices that should be taken into consideration
when applying products such as those described in this publication.
Installation Instructions
Contents
Important User
Information
Vue de la page 0
1 2 3 4 5 6 ... 15 16

Résumé du contenu

Page 1 - Contact Output Module

Publication 1771-IN038B-EN-P - August 2002Contact Output Module(Catalog Number 1771–OWNA)Use this document as a guide when installing the catalog numb

Page 2 - Contact Output Module2

Contact Output Module10Publication 1771-IN038B-EN-P - August 2002!ATTENTIONDo not attempt to increase load current or wattagecapability beyond the ra

Page 3 - Contact Output Module 3

Contact Output Module 11Publication 1771-IN038B-EN-P - August 2002The module has 32 status indicators on the module front plate. Theserepresent the c

Page 4 - Requirements

Contact Output Module12Publication 1771-IN038B-EN-P - August 2002The following information applies when operating this equipment inhazardous location

Page 5 - Connector

Specifications Contact Output Module 13Publication 1771-IN038B-EN-P - August 2002Outputs per module 32 (4 groups of 8)Module Location 1771ĆA1B thru ĆA

Page 6 - Field Wiring Arm

Contact Output Module14Publication 1771-IN038B-EN-P - August 2002Surge Transient Immunity IEC 61000-4-5+1kV line-line (DM) and +2kV line-earth (CM) o

Page 7 - Connect Wiring to the

Contact Output Module 15Publication 1771-IN038B-EN-P - August 2002

Page 8

Contact Output Module16Publication 1771-IN038B-EN-P - August 2002Publication 1771-IN038B-EN-P - August 2002Supersedes Publication 1771-5.38 - October

Page 9 - Output Module

Contact Output Module2Publication 1771-IN038B-EN-P - August 2002Reproduction of the contents of this copyrighted publication, inwhole or part, withou

Page 10 - ATTENTION

Contact Output Module 3Publication 1771-IN038B-EN-P - August 2002ATTENTION!Environment and EnclosureThis equipment is intended for use in a Pollution

Page 11 - Indicators

Contact Output Module4Publication 1771-IN038B-EN-P - August 2002!ATTENTIONPreventing Electrostatic DischargeThis equipment is sensitive to electrosta

Page 12 - RISQUE D'EXPLOSION

Contact Output Module 5Publication 1771-IN038B-EN-P - August 2002Key the BackplaneConnectorPlace your module in any slot in the chassisexcept the lef

Page 13 - Specifications

Contact Output Module6Publication 1771-IN038B-EN-P - August 2002!ATTENTIONRemove power from the 1771 I/O chassisbackplane before you install the modu

Page 14

Contact Output Module 7Publication 1771-IN038B-EN-P - August 2002Make wiring connections to the module through the field wiring arm(cat. no. 1771-WN)

Page 15 - Contact Output Module 15

Contact Output Module8Publication 1771-IN038B-EN-P - August 20023. Make your connections to the field wiring arm as shown in theconnection diagram an

Page 16 - Contact Output Module16

Contact Output Module 9Publication 1771-IN038B-EN-P - August 2002Table AWiring Connections for the 1771-OWNA ContactOutput ModuleTerminalNumberFuncti