DeviceNet Digital Base Terminal Block CompactBlock LDX I/O 25
Publication
1790-IN006C-EN-P - May 2006
DeviceNet Power
Dissipation
1.2 W max @ 28.8V dc
Network Length 500 m (1640 ft) max @ 125 Kbps
100 m (328 ft) max @ 500 Kbps
Network Protocol Slave messaging:
Poll command
Bit Strobe command
Cyclic command
COS command
Indicators 1 red/green module status, 1 red/green network status
Number of Nodes 64 max - rotary switch-type node address setting
Communication Rate 125 Kbps, 250 Kbps, 500 Kbps - auto baud rate selection
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication 1770-4.1.