ControlNet-to-DeviceNet Linking Device 31
Publication
1788-IN052D-EN-P - February 2007
75 Either or both of the following:
The device does not have a scan
list.
The device has not received
communication from any other
device.
Verify that the device has:
a configured scan list.
a properly-wired connection
to the network
76 No direct network traffic for scanner.
The scanner hears other network
communication but does not hear any
directed to it.
None.
77 During initialization, the data size
expected by the device does not
match the scan list entry.
Use RSNetWorx software to
check the slave device and the
scan list for the correct input and
output sizes for the slave device.
DeviceNet Status Codes
Status Code Description of Status Recommended Action