Addressing Rules and Examples
Chapter 4
412
Figure 4.8
Example
of Addressing Specific Bits in PLC/PLC-2 Memory
#H015$0121/010
<
<
<
Bit number 10 (octal)
Delimiter
Word offset from beginning of memory (octal)
Address delimiter
Remote station number
<
Remote data highway station delimiter
10025–I
To specify the address of data at a remote station, use the format shown in
Figure 4.9. This format applies to both PLC–3 and non–PLC–3 remote
stations. The characters #H delimit a remote Date Highway station, and
the characters #M delimit a remote modem station.
Figure 4.9
Example
of Addressing a W
ord in a Remote PLC-3 Station
#H 020 $ B 15:9
<
<
Word address at remote station
Address delimiter
Remote station number 20 (octal)
Port identification for data highway port
Remote station delimiter
#H 020 @ WORD_9
<
<
Symbolic word address defined at remote station
Remote station number 20 (octal)
Port identifier for data highway port
Remote station delimiter
10026-I
Remote station addresses are subject to the following restrictions:
Remote Station Address
Specifications