14 Compact™ 16-Point AC/DC Relay Output Module
Publication 1769-IN062A-EN-P - December 2001
Specifications
General Specifications
Specification Value
Dimensions 118 mm (height) x 87 mm (depth) x 52.5 mm (width)
height including mounting tabs is 138 mm
4.65 in. (height) x 3.43 in (depth) x 2.07 in (width)
height including mounting tabs is 5.43 in.
Approximate Shipping Weight
(with carton)
450g (0.99 lbs.)
Storage Temperature -40°C to +85°C (-40°F to +185°F)
Operating Temperature 0°C to +60°C (32°F to +140°F)
Operating Humidity 5% to 95% non-condensing
Operating Altitude
2000 meters (6561 feet)
(1)
(1) For operation above 2000 meters, consult the factory.
Vibration Operating: 10 to 500 Hz, 5G, 0.030 inches maximum peak-to-peak
Relay Operation: 2.0G
Shock Operating: 30G panel mounted (20G DIN rail mounted)
Relay Operation: 10G panel mounted (5G DIN rail mounted)
Non-Operating: 40G panel mounted (30G DIN rail mounted)
Agency Certification
C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE and C-Tick compliant for all applicable directives
Hazardous Environment Class Class I, Division 2, Hazardous Location, Groups A, B, C, D (UL 1604,
C-UL under CSA C22.2 No. 213)
Radiated and Conducted Emissions EN50081-2 Class A
Electrical /EMC: The module has passed testing at the following levels:
ESD Immunity (IEC61000-4-2) 4kV contact, 8 kV air, 4 kV indirect
Radiated Immunity (IEC61000-4-3)
10 V/m, 80 to 1000 MHz, 80% amplitude modulation, +900
MHz keyed carrier
Fast Transient Burst (IEC61000-4-4)
2 kV, 5 kHz
Surge Immunity (IEC61000-4-5)
2 kV common mode, 1 kV differential mode
Conducted Immunity (IEC61000-4-6)
10V, 0.15 to 80 MHz
(2)
(2) Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz to
1000 MHz.