Compact 1769-OF8V Analog Output Module 23
Publication 1769-IN066D-EN-P - June 2010
Specifications
General Specifications
Specification Value
Dimensions 118 mm (height) x 87 mm (depth) x 35 mm (width)
height including mounting tabs is 138 mm
4.65 in. (height) x 3.43 in (depth) x 1.38 in (width)
height including mounting tabs is 5.43 in.
Approximate Shipping Weight
(with carton)
263g (0.58 lbs.)
Storage Temperature -40°C to +85°C (-40°F to +185°F)
Operating Temperature 0°C to +60°C (32°F to +140°F)
Operating Humidity 5% to 95% non-condensing
Operating Altitude 2000 meters (6561 feet)
Vibration Operating: 10 to 500 Hz, 5G, 0.030 in. peak-to-peak
Relay Operation: 2G
Shock Operating: 30G, 11 ms panel mounted
(20G, 11 ms DIN rail mounted)
Non-Operating: 40G panel mounted
(30G DIN rail mounted)
Agency Certification C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives
Hazardous Environment Class Class I, Division 2, Hazardous Location, Groups A, B, C, D
(ISA 12.12-01, C-UL under CSA C22.2 No. 213)
Radiated and Conducted Emissions EN 61000-6-4 and CISPR 11 Group 1, Class A
Electrical /EMC: The module has passed testing at the following levels:
ESD Immunity (IEC 61000-4-2) 4 kV contact, 8 kV air, 4 kV indirect
Radiated Immunity
(IEC 61000-4-3)
10 V/m, 80 to 1000 MHz, 80% amplitude modulation,
+900 MHz keyed carrier
Fast Transient Burst
(IEC 61000-4-4)
2 kV, 5 kHz
Surge Immunity (IEC 61000-4-5) 1 kV galvanic gun
Conducted Immunity
(IEC 61000-4-6)
10V rms, 0.15 to 80 MHz
(1)
(1)
Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz to
1000 MHz.