Optional - Configuration of the DeviceNet Network Chapter 7
Create a DeviceNet Configuration File
This example shows the steps required create a DeviceNet configuration file using a network
that has already been configured. If you are starting with a network that has not been
configured, the steps are the same, however, the network will appear differently than shown
here.
1. Open RSNetWorx for
DeviceNet software.
2. From the File menu, select
New.
3. Select DeviceNet Configuration and
click OK.
4. Click Who Active to go
online.
5. Expand to the CompactLogix
Backplane and the 1769 Bus.
6. Expand the 1769-SDN and the
DeviceNet Port.
7. Record the 1769-SDN module’s slot
number on the
Network Worksheet
.
In this example, the 1769-SDN module
is in slot 3 of the 1769 Bus and is in
node 1 of the DeviceNet network.
8. Select Port2, DeviceNet and click OK.