Wiring Your Controller 55
Grounding Your Analog Cable
Use shielded communication cable (Belden #8761). The Belden cable has two
signal wires (black and clear), one drain wire, and a foil shield. The drain wire
and foil shield must be grounded at one end of the cable.
IMPORTANT
Do not ground the drain wire and foil shield at
both ends of the cable
Foil shield
Black wire
Drain wire
Clear wire
Insulation
44531