Installing Your Controller 29
Schematic (Using ANSI/CSA Symbols)
Emergency-Stop
Push Button
230V AC
Operation of either of these contacts will
remove power from the external I/O
circuits, stopping machine motion.
Fuse
MCR
Fuse
MCR
MCR
MCR
Stop
Start
Line Terminals: Connect to terminals of Power
Supply (1763-L16AWA, 1763-L16BWA).
Line Terminals: Connect to 24V DC terminals of
Power Supply (1763-L16BBB).
230V AC
Output
Circuits
Disconnect
Isolation
Transformer
115V AC or
230V AC
I/O Circuits
L1
L2
Master Control Relay (MCR)
Cat. No. 700-PK400A1
Suppressor
Cat. No. 700-N24
(Lo)
(Hi)
DC Power Supply. Use
NEC Class 2 for UL
Listing
.
X1
X2
115V AC or
230V AC
_
+
MCR
24 V DC
I/O
Circuits
Suppr.
Overtravel
Limit Switch