118 Troubleshooting the Configurable Flowmeter Module
Determining Fault Type
When you are monitoring a module’s configuration properties in
RSLogix 5000 software and receive a Communications fault message, the
Connection page lists the type of fault.
The fault type is listed here
In this example, Error 16#0011
means Counter 0 was set to an
invalid Operational Mode