Appendix
A
Specifications
This appendix contains the module’s specifications for:
operating power
temperature and humidity
general characteristics
Operating Power
Temperature and
Humidity
Input Line Voltage 18 to 30 V dc
Input Current 104 mA (max) at 24 VDC
Input Volts (ripple) 1V p-p
Input Current Inrush 350 mA pk (max)
Operating Temperature 0 to 55
°
C(+32to+131
°
F)
Storage Temperature -20 to +65
°
C (-4 to +149
°
F)
Humidity Rating
5 to 95% (without condensation)
IMPORTANT: Due to the physical properties of
Liquid Crystal Displays, it is important that the
following temperature/humidity ratings be considered
maximums to prevent premature degradation of
display quality:
Temperature Humidity
35
°
C(95
°
F) 95% RH
45
°
C (113
°
F) 85% RH
55
°
C (131
°
F) 75% RH