4-34
Configuring a Rack Connection
You are now ready to configure the necessary ControlNet connections to read/
write data from the SLC processor to the discrete I/O modules and to the Basic
module. Right click on the 1747-SCNR and choose Scanlist Configuration. (If
you are prompted to enter the edit mode, click YES.) The following screen
appears:
As you can see, the 1747-SCNR and 1747-ACN15 are shown as nodes 1 and 3
respectively. Under the 1747-ACN15, the 3 I/O modules in slots 1 through 3
of the 1747-ACN15 chassis are listed. In order to establish a 16-bit rack
connection to the 1747-ACN15 chassis, right click on the 1747-ACN15 and
choose Insert Connection. The following window opens:
Vue de la page 61