14 ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A
Publication
1738-IN028B-EN-E - February 2010
Adapter Power
Status Description Recommended action
Off Not active; adapter power is off. Apply adapter power.
Green Power is on; 24V input is present. None.
PointBus Status
Status Description Recommended action
Off Device is not online.
- Device has not completed
dup_MAC_id test.
- Device not powered - check
Adapter Status indicator.
Apply power to device, wait for
dup_MAC_id to complete, and
correct, as needed.
Green Device is online and has connections
in the established state.
None.
Flashing
green
Device is online but has no
connections in the established state.
Firmware (NVS) update in progress.
None.
Wait for the firmware update to
complete.
Flashing
red/green
LED cycle power test present. None.
Flashing red Communication faulted device - the
device has detected a network
access error and is in communication
faulted state.
Device has received and accepted an
Identify Communication Faulted
Request - long protocol message.
Verify that adapter is properly
installed, and reinstall, as needed.