Vue de la page 14
POINT I/O Protected Output Module 15
Publication 1734-IN586A-EN-P - December 2001
Environmental Conditions
Operational Temperature IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20 to 55°C (-4 to 131°F)
Storage Temperature IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bc, Unpackaged Nonoperating Dry
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock):
-40 to 85°C (-40 to 185°F)
Relative Humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating
Damp Heat):
5 to 95% non-condensing
Shock
Operating
Non-operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30g peak acceleration
50g peak acceleration
Vibration IEC 60068-2-6, (Test Fc, Operating)
Tested 2g @ 10-500Hz
ESD Immunity IEC 61000-4-2:
6kV contact discharges
8kV air discharges
Radiated RF Immunity IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 80MHz to
1000MHz
EFT/B Immunity IEC 61000-4-4:
±2kV at 5kHz on signal ports
Surge Transient Immunity IEC 61000-4-5:
±1kV line-line(DM) and ±2kV line-earth(CM) on signal
ports
Conducted RF Immunity IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to
80MHz
Emissions CISPR 11;
Group 1, Class A
Enclosure Type Rating None (open-style)
Conductors Wire Size
Category
14 AWG (2.5mm
2
) - 22 AWG (0.25mm
2
) solid or
stranded copper wire rated at 75°C or greater
3/64 inch (1.2mm) insulation maximum
2
2
Terminal Base Screw Torque 7 pound-inches (0.6Nm)
Field Wiring Terminations 0 - Output 0 1 - Output 1
2 - Output 0 3 - Output 1
4 - Common 5 - Common
6 - Supply 7 - Supply
Mass 1.15 oz/32.60 grams