AN-T80004 Field Loop Configuration
Issue 10 Jun 13 AN-T80004 43
Other Issues
System Cable Design
The diagrams below show how to wire the system I/O cables and power supplies for each type of
termination and cable design. Cable choices are shown in the cable PDs TC-200, TC-500, TC-600 and
TC-700.
‘Internal’ cables are protected with a nylon braid and are suitable for use inside a single panel.
‘External’ cables have a sheath but are not armoured and are suitable for routing within a building but
not in trenches.
Analogue or Digital Input module to FTA
Wire the 24V supplies through 3A fuses; the T8193 is designed for this.
FTA
5
TB1
4
3
2
1
Module
24V A
24V B
0V
To Screen Earth
To Safety Earth