Rockwell-automation T7480 ICS Regent+Plus Guarded Analog Output Module Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Équipement Rockwell-automation T7480 ICS Regent+Plus Guarded Analog Output Module. Rockwell Automation T7480 ICS Regent+Plus Guarded Analog Output Modules User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 26
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
ICS Regent+Plus
®
PD
-
7026
Industrial Control Services
1
Guarded Analog Output Modules
4 to 20 mA
(T7480)
Issue 1,
March, 06
Guarded analog output modules provide 4 to 20 mA current
outputs for a maximum of six user loads per module. These
modules are called Guarded because the module'
s dual
-
redundant design ensures that no single fault within a
module will inadvertently change an output's signal. The
module's triplicated Safetybus interface ensures that no
Regent system failure will inadvertently affect the output
signal. Extensive fault detection and annunciation of critical
redundant circuits ensures the modules will continue to
operate in a fail
-
safe manner.
Features
·
Six 4 to 20 mA output circuits.
·
Dual, high resol
ution, 12
-
bit D/A converters per output.
·
Fault tolerant operation when connected in parallel with
another module of the same type.
·
Hot
-
replaceable.
·
Comprehensive self
-
testing of all critical circuits.
·
Front panel indicators on each module show active/fault,
shutdown, and on status.
·
2500 volt minimum electrical isolation between field and lo
gic
circuits.
·
TÜV certified, Risk Class 5, non
-
interfering.
Two Guarded output modules can be connected in parallel to
obtain fault tolerant control of current to the loads. In this
parallel module configuration, either module can be removed
and replaced while the other Guarded module continues to
control the loads without interruption.
Vue de la page 0
1 2 3 4 5 6 ... 25 26

Résumé du contenu

Page 1 - ICS Regent+Plus

ICS Regent+Plus® PD-7026 Industrial Control Services 1 Guarded Analog Output Modules 4 to 20 mA (T7480) Issue 1, March, 06 Guarded analog output mo

Page 2 - Module Operation

Guarded Analog Output Modules (T7480) 10 Industrial Control Services Keying The I/O chassis can be physically keyed to prevent accidental damage c

Page 3

Guarded Analog Output Modules (T7480) PD-7026 Mar-06 11 Figure 5. Installing Slot Keys. Configuration Each output module is configured using

Page 4 - Front Panel Indicators

Guarded Analog Output Modules (T7480) 12 Industrial Control Services 1) Set the Module Type: Position the cursor on the module slot you wish to d

Page 5

Guarded Analog Output Modules (T7480) PD-7026 Mar-06 13 Figure 7. Defining an Analog Output Point. Name Also called the tag name, this is the n

Page 6

Guarded Analog Output Modules (T7480) 14 Industrial Control Services Programming Outputs are controlled by writing application programs that solve

Page 7

Guarded Analog Output Modules (T7480) PD-7026 Mar-06 15 control logic, you maintain the full resolution of the analog output (1 part in 4096) and

Page 8 - Field Wiring

Guarded Analog Output Modules (T7480) 16 Industrial Control Services · Potentiometer adjustment tool. · Phillips screwdriver · I/O module extender

Page 9 - Fault Mode Jumper

Guarded Analog Output Modules (T7480) PD-7026 Mar-06 17 Figure 10. Guarded Analog Output Module Calibration Potentiometer Locations. The I/O

Page 10 - Industrial Control Services

Guarded Analog Output Modules (T7480) 18 Industrial Control Services Figure 11. I/O Extender Connections for Guarded Analog Output Calibration

Page 11

Guarded Analog Output Modules (T7480) PD-7026 Mar-06 19 4. Connect the six precision resistors to the I/O extender jumper posts as shown in Figur

Page 12

Guarded Analog Output Modules (T7480) 2 Industrial Control Services Module Operation A block diagram of the Guarded analog output module is shown

Page 13

Guarded Analog Output Modules (T7480) 20 Industrial Control Services these steps as there may be some interaction between the gain and offset adju

Page 14 - Programming

Guarded Analog Output Modules (T7480) PD-7026 Mar-06 21 the module must be connected (using the I/O extender) to an I/O chassis of an operational

Page 15 - Maintenance

Guarded Analog Output Modules (T7480) 22 Industrial Control Services Figure 12. Location of Test Points for Latent Fault Testing. Testing Step

Page 16 - Important!

Guarded Analog Output Modules (T7480) PD-7026 Mar-06 23 4. Connect the six termination resistors to the I/O extender jumper posts as shown in Fig

Page 17

Guarded Analog Output Modules (T7480) 24 Industrial Control Services fault (green Activity LED turns off and the red Fault LED turns on). 11. Disc

Page 18

Guarded Analog Output Modules (T7480) PD-7026 Mar-06 25 safety of the process should not be dependent on the operations of the guarded analog out

Page 19

Guarded Analog Output Modules (T7480) 26 Industrial Control Services Electromagnetic Interference • IEC 801 Part 2 - Electrostatic Discharges • IE

Page 20

Guarded Analog Output Modules (T7480) PD-7026 Mar-06 3 The combination of redundant interface circuits, D/A converters, and comparison of drive

Page 21

Guarded Analog Output Modules (T7480) 4 Industrial Control Services shunting all six output channel signal outputs to AGND via the diode matrix.

Page 22

Guarded Analog Output Modules (T7480) PD-7026 Mar-06 5 unit is set to shutdown, the red SHUTDOWN indicator will turn on when the communications

Page 23

Guarded Analog Output Modules (T7480) 6 Industrial Control Services Figure 2. Guarded Analog Output Module.

Page 24 - Safety Considerations

Guarded Analog Output Modules (T7480) PD-7026 Mar-06 7 Application Guarded analog output modules are suited for high integrity control of analog

Page 25 - Specifications

Guarded Analog Output Modules (T7480) 8 Industrial Control Services Figure 4. Fault Tolerant Configuration. Field Wiring For field wiring det

Page 26

Guarded Analog Output Modules (T7480) PD-7026 Mar-06 9 Each time the single module enters the standby mode all six of the output channels are ta

Commentaires sur ces manuels

Pas de commentaire