FACTORYTALK VIEW SITE EDITION USER’S GUIDE
14–28
• • • • •
Label Any change New alarm transactions reflect the new Label value.
Existing alarm transactions continue to use the old Label
value.
Severity Any change If the tag is currently in alarm, a new alarm transaction is
generated, based on the new Severity value.
Analog Level Level is added Existing alarm transactions for the tag are removed from
HMI tag alarm summaries.
Level is added or removed If the change results in a new alarm state for the tag, a
new alarm transaction is generated based on the new
state.
Analog Threshold Any change If the change results in a new alarm state for the tag, a
new alarm transaction is generated based on the new
state.
Analog Direction Increasing or Decreasing Existing alarm transactions for the tag are removed from
HMI tag alarm summaries.
If the change results in a new alarm state for the tag, a
new alarm transaction is generated based on the new
state.
Digital Alarm Type On (from Off)
or
Off (from On)
A new alarm transaction is generated.
If the tag is currently in alarm, the transaction is
OutofAlarm; if the tag is currently out of alarm, the
transaction is InAlarm.
Any Change, Changes to On,
or Changes to Off
(from Off or On)
If the tag is currently in alarm, an OutofAlarm transaction
is generated.
On
(from Any Change, Changes
to On, or Changes to Off)
If the tag’s value is On, a new alarm transaction is
generated.
If the tag’s value is Off, no new transaction is generated,
and existing alarm transactions remain in HMI tag alarm
summaries.
Off
(from Any Change, Changes
to On, or Changes to Off)
If the tag’s value is Off, a new alarm transaction is
generated.
If the tag’s value is On, no new transaction is generated,
and existing alarm transactions remain in HMI tag alarm
summaries.
If this property Is changed to this value This is what happens when AlarmAcceptEdits is run