Rockwell-automation DAG6.5.8 APPLICATION GUIDE SCADA SYSTEM Manuel d'utilisateur Page 100

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 420
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 99
Publication AG-UM008C-EN-P - February 2005
3-32 Configuring MicroLogix 1100/1200/1500 Controllers
Figure 3.5 Applying Store and Forward with DF1 Radio Modem Protocol
Figure 3.6 Store & Forward Table for Node 2
Node 4
No Bits
Node 3
1, 2, 4
Node 2
1, 3, 4
Node 1
No Bits
CMD 1
(DST = 4, SRC = 1)
REPLY 1
(DST = 1, SRC = 4)
CMD1
(1st Rebroadcast)
Note 1
(2nd Rebroadcast)
REPLY 1
CMD 1
(2nd Rebroadcast)
(1st Rebroadcast)
REPLY 1
Note 4
Note 2
Note 1 – The link layer of Node 1 blocks the re-transmission of a packet that is received with the SRC byte equal to the
receiving nodes station address. Packets received that originate from the receiving node should never be re-transmitted.
Note 2 – To prevent Node 2 from re-transmitting a duplicate packet, the link layer of Node 2 updates the duplicate packet
table with the last 20 packets received.
Note 3 – The link layer of Node 4 blocks the re-transmission of a packet that is received with the SRC byte equal to the
receiving nodes station address. Packets received that originate from the receiving node should never be re-transmitted.
Note 4 – To prevent Node 3 from re-transmitting a duplicate packet, the link layer of Node 3 updates the duplicate packet
table with the last 20 packets received.
Note 3
Vue de la page 99