Rockwell-automation 57C442 Data Highway Plus Interface Module Manuel d'utilisateur Page 47

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 62
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 46
D-1
Appendix D
Data Highway Plus Interface Module
7-Segment LED Error Codes
The following error codes may be displayed on the 7-segment display.
.0 EPROM checksum failure
0 Gateway parameter error
.1 RAM checksum failure
1 Reply TNS error
.2 RAM AA failure
.3 RAM SS failure
3 Duplicate station detected
.4 RAM address line failure
4 Module not ready
.5 RAM address line clear failure
6 Invalid station address on thumbwheels
7 Module has not been enabled (register 5, bit 0)
.8 Data Highway Plus initialization failure
9 Module re-start in progress
.A Board Reset signal
.b Local watchdog failure
C Local port disconnected
.d AutoMax Processor watchdog failure
.E Power failure
.F Module failure
All errors except 3, 4, 6, 7, and C are fatal errors and indicate a malfunctioning
module.
Vue de la page 46
1 2 ... 42 43 44 45 46 47 48 49 50 51 52 ... 61 62

Commentaires sur ces manuels

Pas de commentaire