17
Bulletin 280G/281G Parameters
Table 9 Starter Display and Parameter Settings
Table 10 FLA Setting Ranges and Default Values (with indicated setting precision)
Parameter Name String Path (hex) Min Max Dflt Type Value
Starter Display
101 Phase A Current 002C – 01 – 08 0 32767 INT xxx.x Amps
102 Phase B Current 002C – 01 – 09 0 32767 INT xxx.x Amps
103 Phase C Current 002C – 01 – 0A 0 32767 INT xxx.x Amps
104 Average Current 002C – 01 – 05 0 32767 INT xxx.x Amps
105 % Therm Utilized 002C – 01 – 07 0 100 USINT xxx %
Starter Settings
106 FLA Setting 002C – 01 – 03 See Table 10 below Min I INT xxx.x Amps
107 OL Trip Class 002C – 01 – 04 0 3 1 BYTE
1 = 10
2 = 15
3 = 20
108 OL Reset Level 0029 – 01 – 131 0 100 75 BYTE xxx %
FLA Current Range (A)
Default Value
Minimum Value Maximum Value
0.5 2.5 0.5
1.1 5.5 1.1
3.2 16.0 3.2
Vue de la page 16