4–2 Downloading 1000e/1200e/1400e Application Files
To prepare the PanelView terminal for a serial download:
1. Using the hardware keyswitch or the Goto Configure Mode
button, switch the PanelView terminal to the Configure mode.
2. In the Terminal Configuration screen, choose the Transfer Setup
button to display the Transfer Setup screen.
3. To change the settings, choose the Baud Rate, Parity, or Error
buttons to move the check mark to the setting you want.
Baud RateĊThe speed at which data is transmitted over the
serial cable. The default setting for a serial transfer is
9600 baud.
ParityĊUsed to check for accurate transmission of the data
between the development computer and terminal. The default
setting is None.
ErrorĊUsed to check for errors in the data transmission.
Error checking is either
CRCĊcyclical (or cyclic) redundancy check.
BCCĊblock check character. BCC is the default setting.
The settings that are defined in the Transfer Setup screen must
match the Transfer Utility’s settings.
4. When you have selected the required settings, choose OK to exit
this screen.
5. To download an application serially, in the Terminal
Configuration screen, choose the Transfer Application button to
display the Transfer Application screen.