Rockwell-automation 25B PowerFlex 525 Embedded EtherNet/IP Adapter Manuel d'utilisateur Page 96

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 166
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 95
96 Rockwell Automation Publication 520COM-UM001B-EN-E - March 2013
Chapter 7 Using Multi-Drive Mode
Correlating the Drive with the Controller
You must now correlate the drive settings to the RSLogix 5000/Logix Designer
project I/O settings so that they match. This requires loading the project I/O
settings into the drive.
1. In the treeview under I/O Configuration, right-click on the drive profile
(for this example “PowerFlex 525-EENET PowerFlex_52X_Drive”) and
select Properties.
2. Select the Drive tab to begin the correlation process.
After the drive configuration data has been verified, the Drive tab will
display a request to synchronize the configuration with the drive. Click
Upload. The correlation process will continue. This may take several
minutes depending on the number and type of daisy-chained drives.
If the Differences Found Screen
on page 97 appears—which is typical,
click Download. This will download the project settings from the
controller to the drives. If Upload is clicked, the drive settings are
uploaded to the controller.
On subsequent connections to the drive (after the initial download),
select Upload.
Vue de la page 95
1 2 ... 91 92 93 94 95 96 97 98 99 100 101 ... 165 166

Commentaires sur ces manuels

Pas de commentaire