Rockwell-automation 20P PowerFlex DC Drive - Frame C Switching Power S Manuel d'utilisateur Page 6

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 8
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 5
6 PowerFlex® DC Drive - Frame C Switching Power Supply Circuit Board
3. Disconnect the cable from connector XSW on the Switching Power
Supply board (see Figure 1 on page 5
for location) and lower the
Control EMI shield until it rests on the drive chassis.
Important: If the drive is not in a vertical position, the Control EMI
shield will not stay open without a means of restraint.
4. Disconnect the cables from connector XA and XUV on the Switching
Power Supply board (see Figure 1 on page 5
for location).
5. If present, disconnect the jumper from terminals SA-SB (see Figure
1 on page 5 for location).
Important: Be sure to replace the jumper between terminals SA-SB if
using 115V AC control input power when installing a new
Switching Power Supply board.
Remove cable
Disconnect cables and wiring
Vue de la page 5
1 2 3 4 5 6 7 8

Commentaires sur ces manuels

Pas de commentaire