10 PowerFlex® DC Drive - Frame C AC Current Transducers
11. Remove the upper screw that secures each of the CTs to the U and W
phase power terminals.
12. Remove the bolt(s) and washer(s) that secure the U and W phase power
terminals to the L-shaped bus bar/fuse.
For Regenerative drives only, remove the two bolts and washers that
secure the U and W phase power terminals to the corresponding
L-shaped bus bars connected to the fuses and while pulling the U and
W phase power terminals down toward the bottom of the drive, slide
the AC Current Transducers off of the terminal bus bar and out of the
drive.
Remove
screw
Note: Left CT and Regenerative drive shown.
Regenerative drive
Remove bolts,
washers and
terminal
Slide AC
Current
Transducers
off of bus bar