Rockwell Automation Publication 193-UM011A-EN-P - September 2010 109
Using DeviceLogix™ Chapter 10
8. Place the cursor on the left of the Bit Output block and press the left
mouse button. Draw a line from the Bit Output block to the Out of the
BOR function block and double-click the left mouse button to establish a
connection.
9. Repeat steps 3 through 8 to add a second BOR function block that
monitors Input 3 and 4 to control Output B of the EC4.
10. Disable Edit mode by de-selecting the Edit mode button or through
the Tools menu.