FLEX I/O Isolated Output HART Analog Module 15
Publication
1794-IN120C-EN-P - April 2009
16 Channel 7 Analog Fault Value Output Data
17 Reserved C
7
C
6
C
5
C
4
C
3
C
2
C
1
C
0
Note: Reserved data may not be shown in certain controller software
(1)
not shown or used in RSLogix 5000.
Configuration Map descriptions
BOA
BOB
Byte order group A
Byte order group B
Byte order group A and B values must match each
other. Refer to the Byte Order table
FT LocalFaultMode 0: Outputs set to safe
value on communication
faults only
1: Outputs set to safe
value on any fault
EWn Fault Enable for wire fault
detection on channel n.
(1)
0: Disable wire off/lead
break detection
1: Enable wire off/lead
break detection
(2)
CHn
HART
Current
Ratio
HART current fault ratio
limit on channel n
Valid values are 0, or 5…31 percent of full scale. A
value of 0 disables this feature. Refer to the HART
Current Ratio table for more information.
AFSn Channel n Analog Fault
Mode Selection
Refer to the Channel Analog Fault Mode Selection
table
Ln Channel n Enable Latching
of wire fault
0: Unlatched 1: Latched
DFn Channel n Digital Fault
Mode Selection
0: Reset (0 mA) 1: Hold Last State
DMn Channel n Enable Digital
Mode
0: Analog 1: Digital
Fn: Fault mode channel n 0: Local/Remote faults
disabled
1: Enabled
Configuration Map
Word Bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0