ArmorBlock MaXum 8 Input / 8 Output Module Series B 11
Publication 1792D-IN020B-EN-P - September 2000
The following table describes logic status indicators.
The following table describes auxiliary power indicators.
The following table describes individual I/O status indicators.
For more information on indications see the Technical Data
publication 1792-TD001B-EN-P.
Net/Mod Status Indicator (continued)
Solid Red Unrecoverable fault
Communication failure - duplicate node address present or incorrect
baud rate
Green to Red to Off At powerup only - LED test
Logic Status Indicators
State Status
Off Logic is disabled
Solid Green Logic is enabled
Flashing Green Local forces are applied and local logic is enabled
Auxiliary Power
Indication Status
None No Auxiliary Power
Green
Solid Auxiliary Power Present
I/O Status Indicators
Function Module Status Indicator
Point Indicator
1
Condition
Outputs Green
Green
Module Status blink red
Module Status blink red
Module Status blink red
Module Status blink red
None
Yellow
Orange
Red
Orange
Red
Output not energized
Output energized
Output shorted-auto restart
Output shorted-latching
Output no load-auto restart
Output no load-latching
Inputs Green
Green
Module Status blink red
Module Status blink red
None
Yellow
Red
Blink red
No valid input
Valid input
Short on input connector
1
Off wire on input connector
1
Only the first LED of each input connector will light as red when twin inputs are used.