8 ArmorBlock LP2 8 Sinking Input Module
Publication 1792D-5.47 - August 1999
The following table describes the network status indicator.
The following table describes I/O status indicators.
For more information on indicators, see the Product Data publication
1792-2.1.
Network Status Indicator
Indication Status
None Not On-line
Green
Blinking
Solid
On-line/No Connections
On-line/Connected
Red
Blink
Solid
Connection Timed Out
Failed Communication: A duplicate node address exists or
module is at the wrong baud rate.
I/O Status Indicators
Function Module Status Indicator Point Indicator Condition
Inputs Green
Green
Blinking Red
None
Yellow
None
No valid input
Valid input
Input Short