6 ArmorBlock MaXum 12 Input/ 4 Output Module Series B
Publication 1792D-IN004B-EN-P - August 2000
Use the micro caps to cover and seal unused ports. Pinout diagrams
for the connectors are shown next.
Molded I/O cables with LEDs embedded in the connector are
incompatible with MaXum universal sink/source inputs. Please refer
to publication 889-5.0 for Rockwell Automation cables and cord sets
offerings.
IMPORTANT
If the devices (sensors) connected to the input
connections require Class 2 power to operate, the
DeviceNet connections of this equipment must be
powered by a Class 2 source.
ATTENTION
!
Make sure all connectors and caps are
securely tightened to properly seal the
connections against leaks and maintain
IP67 requirements.
For maximum noise immunity, input and
output cable return wires must be properly
terminated. When inputs and outputs are
connected in loopback, return wires should
be connected together.
I/O cable length should be less than 30
meters.
Input Micro-Connector
(View into Socket)
Pin 1 Sensor Source voltage
Pin 2 Input B
Pin 3 Return Logic Ground
1
Pin 4 Input A
Pin 5 Not Used
Output Micro-Connector
(View into Socket)
Pin 1 Not Used
Pin 2 Output B
Pin 3 Auxiliary Power Ground
Pin 4 Output A
Pin 5 Not Used
41452
1
Logic Ground is approximately 0.4V above DeviceNet V- measured at the module.