Rockwell-automation 1785-Lx0C15 ControlNet PLC-5 Programmable Controll Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Équipement Rockwell-automation 1785-Lx0C15 ControlNet PLC-5 Programmable Controll. Rockwell Automation 1785-Lx0C15 ControlNet PLC-5 Programmable Controllers User Manual User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 148
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs

Résumé du contenu

Page 1 - Controllers

User Manual(Catalog Numbers 1785-L20C15, 1785-L40C15, 1785-L46C15, 1785-L80C15)ControlNet PLC-5 Programmable Controllers

Page 2 - Important User Information

1785-UM022C-EN-P - February 2008Preface-2TerminologyTerm DescriptionActual Packet Interval (API) the actual time it takes for the ControlNet network t

Page 3 - Summary of Changes

1785-UM022C-EN-P - February 2008A-4The following information applies when operating this equipment in hazardous locations:Informations sur l’utilisati

Page 4

1785-UM022C-EN-P - February 2008Appendix BProcessor Status FileS:0 - S:2 Processor status data is stored in data-file 2. This word of the status file:

Page 5 - Table of Contents

1785-UM022C-EN-P - February 2008B-2 Processor Status FileS:3-10S:2/07 S:2/08Not definedS:2/09 Last state0 outputs are turned off1 outputs retain last

Page 6 - Chapter 3

1785-UM022C-EN-P - February 2008Processor Status File B-3S:11S:10/04 Edits prevent SFC continuing; data table size changed during program mode; reset

Page 7 - Appendix C

1785-UM022C-EN-P - February 2008B-4 Processor Status FileS:12 This word stores the following fault codes:S:11/12 PII file does not exist or is not a l

Page 8 - Appendix E

1785-UM022C-EN-P - February 2008Processor Status File B-510 Run-time data table check failed Recoverable: the fault routine can instruct the processor

Page 9

1785-UM022C-EN-P - February 2008B-6 Processor Status File41 NXT instruction with missing FOR Non-recoverablethe fault routine will be executed but ca

Page 10 - Terminology

1785-UM022C-EN-P - February 2008Processor Status File B-783 User watchdog fault Recoverable84 Error in user-configured adapter mode block-transfer85 M

Page 11

1785-UM022C-EN-P - February 2008B-8 Processor Status File201 ControlNet input data missed.The processor is unable to process incoming data from the ne

Page 12

1785-UM022C-EN-P - February 2008Processor Status File B-9205 ControlNet configuration exceeds processor bandwidth.IMPORTANT: Scheduled connections wil

Page 13 - PLC-5 Processor

1785-UM022C-EN-P - February 2008Preface-3repeater two-port active physical-layer device that reconstructs and retransmits all traffic that it hears on

Page 14

1785-UM022C-EN-P - February 2008B-10 Processor Status File231 Bypassed qualification (may occur during race condition when both processors attempt to

Page 15 - Processor Components

1785-UM022C-EN-P - February 2008Processor Status File B-11S:13-S:24This word of the status file:Stores:S:13 Program file where fault occurredS:14 Rung

Page 16

1785-UM022C-EN-P - February 2008B-12 Processor Status FileS:26-S:35S:23 Processor clock secondS:24 Indexed addressing offsetS:25 ReservedThis word of

Page 17 - Programmable Controller

1785-UM022C-EN-P - February 2008Processor Status File B-13Important: Setting inhibit bits in the processor status file (S:27, S:33, or S:35) does not

Page 18

1785-UM022C-EN-P - February 2008B-14 Processor Status FileS:64 The number of remote block-transfer command blocks being used by channel pair 1A/1B.S:6

Page 19

1785-UM022C-EN-P - February 2008Processor Status File B-15S:79-S127This word of the status file:Stores:S:79 MCP inhibit bitsBit 0 for MCP A Bit 1 for

Page 20 - Dispose of a Battery

1785-UM022C-EN-P - February 2008B-16 Processor Status FileNotes

Page 21 - Backplane Switches

1785-UM022C-EN-P - February 2008Appendix CControlNet Instruction SetFor detailed information about the instruction set for programming PLC-5 processor

Page 22 - Installing Keying Bands

1785-UM022C-EN-P - February 2008C-2 ControlNet Instruction SetImmediate Data I/O Instructions Immediate I/O Execution TimesInstruction Descripti

Page 23 - Address of Channel 1A

1785-UM022C-EN-P - February 2008Appendix DControlNet I/O Map-Entry Status Words and Error Codes I/O Map-Entry Status WordsThe ControlNet status fil

Page 24 - Channel 2

1785-UM022C-EN-P - February 2008Preface-4Related PLC-5 Publications The 1785 PLC-5 programmable-controller and ControlNet documentation is organized i

Page 25 - I/O Link

1785-UM022C-EN-P - February 2008D-2 ControlNet I/O Map-Entry Status Words and Error CodesThe following table explains the bits in the first word of th

Page 26

1785-UM022C-EN-P - February 2008ControlNet I/O Map-Entry Status Words and Error Codes D-3The following table explains the second and third status word

Page 27

1785-UM022C-EN-P - February 2008D-4 ControlNet I/O Map-Entry Status Words and Error CodesError Codes The following is a list of ControlNet error codes

Page 28

1785-UM022C-EN-P - February 2008ControlNet I/O Map-Entry Status Words and Error Codes D-538 0x0026 INVALID DESTINATION ADDRESS SIZEThe map table is co

Page 29 - ControlNet Network

1785-UM022C-EN-P - February 2008D-6 ControlNet I/O Map-Entry Status Words and Error Codes279 0x0117 INVALID CONNECTION POINT The PLC-5C is requesting

Page 30

1785-UM022C-EN-P - February 2008ControlNet I/O Map-Entry Status Words and Error Codes D-7516 0x0204 UNCONNECTED REQUEST TIMED OUTThe ControlNet cable

Page 31 - Programming Terminal

1785-UM022C-EN-P - February 2008D-8 ControlNet I/O Map-Entry Status Words and Error Codes774 0x0306 KEEPER NOT AVAILABLE The ControlNet cable from the

Page 32 - Serial Channel

1785-UM022C-EN-P - February 2008ControlNet I/O Map-Entry Status Words and Error Codes D-965523 0xFFF3 CONTROLNET TRANSFER QUEUE FULLThe immediate CIO

Page 33 - ControlNet Connection

1785-UM022C-EN-P - February 2008D-10 ControlNet I/O Map-Entry Status Words and Error Codes65530 0xFFFA MODULE DECLARED INVALID LENGTHA communication e

Page 34 - Serial Cables

1785-UM022C-EN-P - February 2008ControlNet I/O Map-Entry Status Words and Error Codes D-11Notes

Page 35 - ControlNet Cables

1785-UM022C-EN-P - February 2008Chapter 1Installing Your ControlNet PLC-5 ProcessorUsing This ChapterFor detailed information about installing chassi

Page 36

1785-UM022C-EN-P - February 2008D-12 ControlNet I/O Map-Entry Status Words and Error Codes

Page 37

1785-UM022C-EN-P - February 2008Appendix EFault CodesFault routines execute when a PLC-5 processor encounters a run-time error (major fault) during pr

Page 38

1785-UM022C-EN-P - February 2008E-2 Fault Codes205 ControlNet configuration exceeds processor resources.IMPORTANT: Scheduled connections will be close

Page 39 - Processor

1785-UM022C-EN-P - February 2008Appendix FControlNet Diagnostics File LayoutWhen you specify a Control Diagnostic File in RSNetWorx for the ControlNet

Page 40

1785-UM022C-EN-P - February 2008F-2Node Address of current Moderator 15;15-08Cannot Hear Moderator Occurrences (i.e., Lonely) 16;07-00Network Paramete

Page 41 - I/O Chassis

1785-UM022C-EN-P - February 2008F-3The following table describes each bit in word 23 (Channel status and Media bits) of the diagnostic file.Maximum nu

Page 42

1785-UM022C-EN-P - February 2008F-4Notes

Page 43 - . . .. .

Publication 1785-UM022C-EN-P - February 2008IndexNumerics1747 modulesdiscrete I/O data transfer mapping 2-201770-CD 1-15, 1-231770-KFC Communication I

Page 44

Publication 1785-UM022C-EN-P - February 20082 IndexControlNet I/Oerror messages D-4features 2-1files configured with mapData Input File (DIF) 2

Page 45 - Using I/O Forcing Operations

Publication 1785-UM022C-EN-P - February 2008Index 3ControlNet systemcabling 1-23configuring 3-1changing a 1794 I/O modules fault action 2-6, 4-

Page 46 - Logic Scan

1785-UM022C-EN-P - February 20081-2 Installing Your ControlNet PLC-5 ProcessorPrevent Electrostatic DischargeThis equipment is sensitive to electrosta

Page 47

Publication 1785-UM022C-EN-P - February 20084 IndexII/OControlNet 2-1automatic mapping 2-16discrete I/O data transfer mapping 2-19files configu

Page 48 - PCSC Enable Bit

Publication 1785-UM022C-EN-P - February 2008Index 5locating additional information 1-1removing the processor from the chassis 1-13selecting cab

Page 49 - Connection Types

Publication 1785-UM022C-EN-P - February 20086 IndexPPCMCIA Communication Card 2-31PCSC 2-9considerations 2-11PCSC enable bit D-2PCSC new data b

Page 50

Publication 1785-UM022C-EN-P - February 2008Index 7terminating 1-17Selectable Timed Interrupts (STIs)using with ControlNet system 4-9selecting

Page 51

Publication 1785-UM022C-EN-P - February 20088 Index

Page 52

Publication CIG-CO521D-EN-P- July 2007How Are We Doing?Your comments on our technical publications will help us serve you better in the future.Thank

Page 53

Other CommentsPLEASE FOLD HERENO POSTAGE NECESSARY IF MAILED IN THE UNITED STATESBUSINESS REPLY MAILFIRST-CLASS MAIL PERMIT NO. 18235 CLEVELAND OHPOST

Page 55

Publication 1785-UM022C-EN-P - February 2008 20Supersedes Publication 1785-UM022B-EN-P - February 2002 Copyright © 2008 Rockwell Automation, Inc. All

Page 56

1785-UM022C-EN-P - February 2008Installing Your ControlNet PLC-5 Processor 1-3Identifying ControlNet PLC-5 Processor ComponentsFigure 1.1 and Figure 1

Page 57

1785-UM022C-EN-P - February 20081-4 Installing Your ControlNet PLC-5 ProcessorFigure 1.2 PLC-5/40C, -5/46C, and -5/80C Processors Front PanelBattery S

Page 58

1785-UM022C-EN-P - February 2008Installing Your ControlNet PLC-5 Processor 1-5Before You Install the Programmable ControllerBefore installing your Con

Page 59 - RPI Default = 4 x NUT

1785-UM022C-EN-P - February 20081-6 Installing Your ControlNet PLC-5 ProcessorInstall or Replace the Battery A 3.0 volt lithium battery (cat. no. 1770

Page 60

1785-UM022C-EN-P - February 2008Installing Your ControlNet PLC-5 Processor 1-7To install or replace the battery:1. Remove the battery from the shippin

Page 61

Important User InformationSolid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines

Page 62

1785-UM022C-EN-P - February 20081-8 Installing Your ControlNet PLC-5 ProcessorEstimated Battery LifetimesDispose of a BatteryIf you need to dispose of

Page 63 - I:010 6 O:010 2

1785-UM022C-EN-P - February 2008Installing Your ControlNet PLC-5 Processor 1-9Setting the I/O Chassis Backplane SwitchesSet the I/O chassis backplane

Page 64

1785-UM022C-EN-P - February 20081-10 Installing Your ControlNet PLC-5 ProcessorSetting the I/O Chassis Configuration PlugSet the I/O chassis configura

Page 65

1785-UM022C-EN-P - February 2008Installing Your ControlNet PLC-5 Processor 1-11Selecting the DH+ Station Address of Channel 1ATo select the DH+ stati

Page 66

1785-UM022C-EN-P - February 20081-12 Installing Your ControlNet PLC-5 ProcessorSpecifying the Serial Interface of Channel 0Specify RS-232C, RS-422A,

Page 67

1785-UM022C-EN-P - February 2008Installing Your ControlNet PLC-5 Processor 1-13Inserting/Removing the Processor into/from the I/O ChassisTo insert/rem

Page 68

1785-UM022C-EN-P - February 20081-14 Installing Your ControlNet PLC-5 ProcessorIf your remote I/O link:Use this resistor rating:The maximum number ofp

Page 69 - ControlNet I/O System

1785-UM022C-EN-P - February 2008Installing Your ControlNet PLC-5 Processor 1-15Installing a DH+ Link Use 1770-CD cable to connect the processor to a D

Page 70 - 1786-TPR

1785-UM022C-EN-P - February 20081-16 Installing Your ControlNet PLC-5 ProcessorIf you connect or disconnect the 1770-CD cable with power applied to th

Page 71

1785-UM022C-EN-P - February 2008Installing Your ControlNet PLC-5 Processor 1-17CH 0BATTCH 0Connecting to a ControlNet NetworkConnect a ControlNet PLC

Page 72 - I/O System

1785-UM022C-EN-P - February 2008Summary of Changes The information below summarizes the changes to the ControlNet PLC-5 Programmable Controllers User

Page 73 - 1.5 system

1785-UM022C-EN-P - February 20081-18 Installing Your ControlNet PLC-5 ProcessorFor detailed information about planning and installing your ControlNet

Page 74

1785-UM022C-EN-P - February 2008Installing Your ControlNet PLC-5 Processor 1-19Connecting a Programming TerminalYou can connect a programming termina

Page 75 - System Software

1785-UM022C-EN-P - February 20081-20 Installing Your ControlNet PLC-5 ProcessorSerial ChannelTo program the processor using Channel 0, configure the c

Page 76 - I/O Configuration Utility

1785-UM022C-EN-P - February 2008Installing Your ControlNet PLC-5 Processor 1-21ControlNet ConnectionYou can connect programming devices to a ControlNe

Page 77 - Information

1785-UM022C-EN-P - February 20081-22 Installing Your ControlNet PLC-5 ProcessorSelecting Appropriate Cables This section lists information about:• ser

Page 78

1785-UM022C-EN-P - February 2008Installing Your ControlNet PLC-5 Processor 1-23This processor’s serial port can support these configurations:Important

Page 79

1785-UM022C-EN-P - February 20081-24 Installing Your ControlNet PLC-5 ProcessorThe following ControlNet cable system components are available from the

Page 80

1785-UM022C-EN-P - February 2008Installing Your ControlNet PLC-5 Processor 1-25For detailed information about ControlNet cabling, see the following pu

Page 81 - Programming Your

1785-UM022C-EN-P - February 20081-26 Installing Your ControlNet PLC-5 ProcessorNotes

Page 82 - ControlBus

1785-UM022C-EN-P - February 2008Chapter 2Planning to Use Your ControlNet PLC-5 ProcessorUsing This ChapterTo distinguish phase 1.5 ControlNet processo

Page 83 - Transfer Instruction

1785-UM022C-EN-P - February 2008SOC-iiNotes

Page 84

1785-UM022C-EN-P - February 20082-2 Planning to Use Your ControlNet PLC-5 ProcessorScheduled Data-Transfer Operations on a ControlNet NetworkControlNe

Page 85 - Sending Continuous Messages

1785-UM022C-EN-P - February 2008Planning to Use Your ControlNet PLC-5 Processor 2-3The frequency of I/O chassis backplane updates depends on the adapt

Page 86 - Output Instructions

1785-UM022C-EN-P - February 20082-4 Planning to Use Your ControlNet PLC-5 ProcessorThe following scheduled data-transfer operations are supported by t

Page 87 - N11:232 232

1785-UM022C-EN-P - February 2008Planning to Use Your ControlNet PLC-5 Processor 2-5The ControlNet system places your scheduled transfers in the first

Page 88 - N12:175 175

1785-UM022C-EN-P - February 20082-6 Planning to Use Your ControlNet PLC-5 ProcessorTable 2.B ControlNet Unscheduled Data-Transfer OperationsOperation

Page 89 - Interrupts with a Program

1785-UM022C-EN-P - February 2008Planning to Use Your ControlNet PLC-5 Processor 2-7Using I/O Forcing OperationsControlNet I/O forcing occurs in the sa

Page 90

1785-UM022C-EN-P - February 20082-8 Planning to Use Your ControlNet PLC-5 ProcessorUsing Immediate Data-Transfer OperationsControlNet Immediate Data I

Page 91 - Your ControlNet System

1785-UM022C-EN-P - February 2008Planning to Use Your ControlNet PLC-5 Processor 2-9Table 2.C ControlNet Immediate Data-Transfer OperationsUsing Proces

Page 92

1785-UM022C-EN-P - February 20082-10 Planning to Use Your ControlNet PLC-5 ProcessorYou enable process control sample complete on a per connection bas

Page 93 - Status Indicators

1785-UM022C-EN-P - February 2008Planning to Use Your ControlNet PLC-5 Processor 2-11Clearing the PCSC New Data and PCSC Overflow BitsIf it is crucial

Page 94

Table of Contents1785-UM022C-EN-P - February 2008Installing Your ControlNet PLC-5 ProcessorChapter 1Using This Chapter . . . . . . . . . . . . . . .

Page 95 - Using the DH+/RIO

1785-UM022C-EN-P - February 20082-12 Planning to Use Your ControlNet PLC-5 ProcessorThere are four general types of scheduled connections from the Con

Page 96 - Configuration and Status

1785-UM022C-EN-P - February 2008Planning to Use Your ControlNet PLC-5 Processor 2-13If an input only connection is made to the adapter:• an exclusive

Page 97 - Processor Specifications

1785-UM022C-EN-P - February 20082-14 Planning to Use Your ControlNet PLC-5 ProcessorUnderstanding Multicast InputsThis feature enables input devices t

Page 98

1785-UM022C-EN-P - February 2008Planning to Use Your ControlNet PLC-5 Processor 2-15Using Multicast OutputsTo use multicast outputs, you must first co

Page 99

1785-UM022C-EN-P - February 20082-16 Planning to Use Your ControlNet PLC-5 ProcessorUnderstanding ControlNet I/O MappingAll scheduled data transfers

Page 100 - AVERTISSMENT

1785-UM022C-EN-P - February 2008Planning to Use Your ControlNet PLC-5 Processor 2-17Remote I/OThe following table shows the default number of input an

Page 101 - Processor Status File

1785-UM022C-EN-P - February 20082-18 Planning to Use Your ControlNet PLC-5 ProcessorSupported ControlNet I/O SizesThe following table shows the maximu

Page 102

1785-UM022C-EN-P - February 2008Planning to Use Your ControlNet PLC-5 Processor 2-19Discrete I/O Data-Transfer MappingRegardless of the type of I/O—e.

Page 103

1785-UM022C-EN-P - February 20082-20 Planning to Use Your ControlNet PLC-5 Processor1771 ModulesControlNet 1771 discrete I/O data-transfer mapping req

Page 104

1785-UM022C-EN-P - February 2008Planning to Use Your ControlNet PLC-5 Processor 2-21Other ControlNet ProcessorsControlNet scheduled peer-to-peer commu

Page 105

ii Table of Contents – ControlNet PLC-5 Programmable Controllers1785-UM022C-EN-P - February 2008Understanding Multicast Inputs . . . . . . . . . . . .

Page 106

1785-UM022C-EN-P - February 20082-22 Planning to Use Your ControlNet PLC-5 ProcessorUnderstanding Discrete MappingEach version of a PLC-5 processor ha

Page 107

1785-UM022C-EN-P - February 2008Planning to Use Your ControlNet PLC-5 Processor 2-23Optimizing the I/O Image TableYou may find that you are close to t

Page 108

1785-UM022C-EN-P - February 20082-24 Planning to Use Your ControlNet PLC-5 ProcessorIf you perform an automap on this system, the map table appears li

Page 109

1785-UM022C-EN-P - February 2008Planning to Use Your ControlNet PLC-5 Processor 2-25First Rule of Module OptimizationWhen placing discrete modules, pu

Page 110

1785-UM022C-EN-P - February 20082-26 Planning to Use Your ControlNet PLC-5 ProcessorSecond Rule of Module OptimizationPlace modules that do not requir

Page 111 - S:13-S:24

1785-UM022C-EN-P - February 2008Planning to Use Your ControlNet PLC-5 Processor 2-27Example 4Examine the following system:Assume you want to add an ad

Page 112 - S:26-S:35

1785-UM022C-EN-P - February 20082-28 Planning to Use Your ControlNet PLC-5 ProcessorExample 1Examine the following chassis: In this example the first

Page 113 - S:36-S:78

1785-UM022C-EN-P - February 2008Planning to Use Your ControlNet PLC-5 Processor 2-29SummaryThere are two methods to optimize the use of I/O image tabl

Page 114

1785-UM022C-EN-P - February 20082-30 Planning to Use Your ControlNet PLC-5 ProcessorHowever, the overall system may be heavy on inputs, and there are

Page 115 - S:79-S127

1785-UM022C-EN-P - February 2008Planning to Use Your ControlNet PLC-5 Processor 2-31Using the ControlNet PLC-5 Processor in a ControlNet I/O SystemThe

Page 116 - B-16 Processor Status File

Table of Contents – ControlNet PLC-5 Programmable Controllers iii1785-UM022C-EN-P - February 2008Programming Your ControlNet SystemChapter 4Using Thi

Page 117 - ControlNet Instruction Set

1785-UM022C-EN-P - February 20082-32 Planning to Use Your ControlNet PLC-5 ProcessorPersonal computerwith 1784-KTCX15 card(ISA-based) andyour HMI orpr

Page 118 - Immediate I/O Execution Times

1785-UM022C-EN-P - February 2008Planning to Use Your ControlNet PLC-5 Processor 2-33Distributed Keeper FunctionalityAll ControlNet processors now keep

Page 119 - Error Codes

1785-UM022C-EN-P - February 20082-34 Planning to Use Your ControlNet PLC-5 ProcessorConverting from a Non-ControlNet Remote I/O System to a ControlNet

Page 120 - ControlNet I/O status file:

1785-UM022C-EN-P - February 2008Planning to Use Your ControlNet PLC-5 Processor 2-35 Converting from ControlNet Phase 1.0 or 1.25 to ControlNet Phase

Page 121 - ControlNet I/O status file

1785-UM022C-EN-P - February 20082-36 Planning to Use Your ControlNet PLC-5 ProcessorNotes

Page 122

1785-UM022C-EN-P - February 2008Chapter 3Understanding the ControlNet System SoftwareUsing This Chapter This chapter describes the configuration and p

Page 123

1785-UM022CEN-P - February 20083-2 Understanding the ControlNet System SoftwareAlso, the ControlNet network requires that the entire network be config

Page 124

1785-UM022C-EN-P - February 2008Understanding the ControlNet System Software 3-3Under these circumstances, consider the following guidelines:• when co

Page 125

1785-UM022CEN-P - February 20083-4 Understanding the ControlNet System SoftwareDownload from both RSNetWorx and RSLogix 5 softwareYou can download the

Page 126

1785-UM022C-EN-P - February 2008Understanding the ControlNet System Software 3-5To verify keeper signatures:1. In Network menu, choose Keeper Status2.

Page 127

iv Table of Contents – ControlNet PLC-5 Programmable Controllers1785-UM022C-EN-P - February 2008ControlNet I/O Map-Entry Status Words and Error Mess

Page 128

1785-UM022CEN-P - February 20083-6 Understanding the ControlNet System SoftwareNotes

Page 129

1785-UM022C-EN-P - February 2008Chapter 4Programming Your ControlNet SystemUsing This ChapterUsing ControlNet Message InstructionsYou can use the Mes

Page 130

1785-UM022C-EN-P - February 20084-2The fields of the MG data type that you can directly address are:For more detailed information about writing ladder

Page 131 - Fault Codes

1785-UM022C-EN-P - February 20084-3Option to Close Communication Connection when MSG is DoneThis feature allows you to configure the ControlNet ladder

Page 132

1785-UM022C-EN-P - February 20084-4If you want to: Do this:change the command typeSelect one of the following:• 1771 READ - reads input data from 1771

Page 133 - Appendix F

1785-UM022C-EN-P - February 20084-5The fields of the CT data type that you can directly address are:The CIP Generic and Generic Bi-directional CIO com

Page 134

1785-UM022C-EN-P - February 20084-61771 ControlNet Transfers in PIIs and STIsWhen a 1771 Read or 1771 Write CIO instruction is encountered in a PII or

Page 135

1785-UM022C-EN-P - February 20084-7In the previous example, an IDI is initiated that updates the destination file from the private buffer before the n

Page 136

1785-UM022C-EN-P - February 20084-8An IDO is initiated that updates the private memory output buffer from the source file before the next normal outpu

Page 137 - Numerics

1785-UM022C-EN-P - February 20084-9Using Selectable Timed Interrupts with a Program on a ControlNet NetworkYou must be careful when using Selectable T

Page 138 - 2 Index

1785-UM022C-EN-P - February 2008PrefaceIntroduction This manual describes how to install your programmable controller and how to plan for, configure,

Page 139 - Index 3

1785-UM022C-EN-P - February 20084-10Notes

Page 140 - 4 Index

1785-UM022C-EN-P - February 2008Chapter 5Monitoring and Troubleshooting Your ControlNet SystemUsing This ChapterUsing the General Status IndicatorsTh

Page 141 - Index 5

1785-UM022C-EN-P - February 20085-2PROC Green (steady)Processor is in run mode and fully operationalNormal operation No action requiredGreen (blinking

Page 142 - 6 Index

1785-UM022C-EN-P - February 20085-3Using the ControlNet Status IndicatorsThe ControlNet status indicators inform you of the operational state of the C

Page 143 - Index 7

1785-UM022C-EN-P - February 20085-4IndicatorColor1Probable Cause Recommended ActionOff Channel disabled No action requiredConfigure for ControlNet com

Page 144 - 8 Index

1785-UM022C-EN-P - February 20085-5Using the DH+/RIO Status IndicatorsIndicator Color Channel Mode Description Probable Cause Recommended ActionGreen

Page 145 - How Are We Doing?

1785-UM022C-EN-P - February 20085-6Monitoring ControlNet Configuration and StatusUse the following software packages to monitor ControlNet configurati

Page 146 - BUSINESS REPLY MAIL

1785-UM022C-EN-P - February 2008Appendix AProcessor Specifications Backplane Current 1785-L20C15: 2.7A @ 5Vdc1785-L40C15, -L46C15, -L80C15: 3.3A @ 5V

Page 147

1785-UM022C-EN-P - February 2008A-2Hardware Addressing 2-slot• Any mix of 8-pt modules• 16-pt modules must be I/O pairs• No 32-pt modules1-slot• Any m

Page 148 - Rockwell Automation

1785-UM022C-EN-P - February 2008A-3PLC-5/20C15 PLC-5/40C15 PLC-5/46C15 PLC-5/80C15Maximum User Memory Words 16K48K148K1100K2Maximum Total I/OAny Mix 5