Chapter
Call Routines 0–68
12
12 -53
Once this call is active, it remains active and sends data to the remote node
whenever the PLC processor handshaking is accomplished.
Input and Output Arguments
This call has ten input arguments and one output argument.
Argument Description Page
input 1
type of DH-485 WRITE 12 -53
input 2 node address of the DH-485 remote device (0 through 31) 12 -53
input 3 file number on the DH-485 remote device (0 through 255) 12 -53
input 4 file type to be written to the remote device 12 -54
input 5 starting word offset within the file on the remote device (0
through 32766)
12 -54
input 6 number of words to be transferred 12 -54
input 7 the message time-out value 12 -54
input 8 the selection of the source BTW buffer or internal string 12 -55
input 9 always 1 12 -55
input 10 the string number 12 -55
output 1 call status 12 -55
To disable this call, you must PUSH a zero into the first input parameter.
All other parameters are ignored but you must still PUSH them.
Input Argument One
The first input argument is the type of DH-485 WRITE command issued:
0 = disable the previously executed CALL 50
1 = common interface file write
2 = SLC typed write
Input Argument Two
The second input argument is the node address of the DH-485 remote
device on the DH-485 network (0 through 31). If the number is not within
this range, the status equals 2 and the write message does not occur.
Input Argument Three
The third input argument is the file number on the DH-485 remote device
(0 through 255). If the number is not within this range, the status equals 2
and the write message does not occur.