Rockwell-automation 1769-IG16 Compact TTL Input Module Manuel d'utilisateur Page 16

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 20
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 15
16 Compact TTL Input Module
Publication 1769-IN079A-EN-P - May 2006
Environmental Specifications
Attribute Value
Storage Temperature -40…+85 °C (-40…+185°F)
Operating Temperature 0…60 °C (32…140 °F)
Operating Humidity 5…95% non-condensing
Operating Altitude 2000 m (6561 ft)
Vibration Operating: 10…500 Hz, 5 g, 0.030 in. max peak-to-peak
Shock Operating: 30 g panel mounted (20 g DIN-rail mounted)
Non-operating: 40 g panel mounted (30 g DIN-rail mounted)
Radiated and Conducted
Emissions
EN50081-2 Class A
Electrical /EMC The module has passed testing at the following levels
ESD Immunity (IEC61000-4-2) 4 kV contact, 8 kV air, 4 kV indirect
Radiated Immunity (IEC61000-4-3) 10V/m, 80…1000 MHz, 80% amplitude
Fast Transient Burst
(IEC61000-4-4)
2 kV, 5 kHz
Conducted Immunity
(IEC61000-4-6)
10V, 0.15…80 MHz
(1)
(1)
Conducted Immunity frequency range may be 150 kHz…30 MHz if the radiated immunity frequency range is 30…1000 MHz.
Certifications
Attribute Value
Agency Certification • C-UL certified (under CSA C22.2 No. 142)
• UL 508 listed
• CE compliant for all applicable directives
Hazardous Environment Class Class I, Division 2, Hazardous Location, Groups A, B, C, D
(UL 1604, C-UL under CSA C22.2 No. 213)
Vue de la page 15
1 2 ... 11 12 13 14 15 16 17 18 19 20

Commentaires sur ces manuels

Pas de commentaire