Compact I/O 1769-IF8 Analog Input Module 17
Publication 1769-IN067B-EN-P - September 2005
Define To Select Make these bit settings
15 14 13 12 11 10 9 8 7-4 3 2 1 0
Input Filter
Selection/
-3 dB
Frequency
60 Hz 0 0 0 0
50 Hz 0 0 0 1
10 Hz 0 0 1 0
250 Hz 0 0 1 1
500 Hz 0 1 0 0
Enable
Interrupt
Enable 1
Disable 0
Process
Alarm Latch
Enable 1
Disable 0
Enable
Process
Alarms
Enable 1
Disable 0
Enable
Channel
Enable 1
Disable 0
Define Indicate this These bit settings
15-11 10 9 8 7-4 3 2 1 0
Input
Range
Select
-10 to +10V dc 0 0 0 0
0 to 5V dc 0 0 0 1
0 to 10V dc 0 0 1 0
4 to 20 mA 0 0 1 1
1 to 5V dc 0 1 0 0
0 to 20 mA 0 1 0 1
Input Data
Select
Raw/Proportional
Counts
0 0 0
Engineering Units 0 0 1
Scaled for PID 0 1 0
Percent Range 0 1 1