Module Addressing and Configuration with MicroLogix 1500 73
Input Image
The module's input image file represents input states and output data echo
states. Input word 0 holds the input data that represents the value of inputs
IN0 to IN7. Input word 1 represents the directed state of the module's outputs
OUT0 through OUT3.
For example, to obtain the state of input IN2 of the module when it is in slot
3, use address I:3.0/2.
TIP
The end cap does not use a slot address.
I:3.0/2
Input File Type
Slot
Word
Bit
Bit Delimiter
Word Delimiter
Element Delimiter
0123
MicroLogix 1500
Compact I/O
Compact I/O
Compact I/O
End Cap
Slot Number