Rockwell-automation 1769-ADN Compact I/O DeviceNet Adapter Manuel d'utilisateur Page 21

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 28
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 20
Compact I/O 1769-ADN DeviceNet Adapter 21
Rockwell Automation Publication 1769-IN001C-EN-P - February 2013
Network Status (NS)
OFF No power or no network access
Flashing GRN/OFF On-line but not connected
Solid GRN On-line and connected
Flashing RED/OFF Connection time-out
Solid RED Critical network failure
I/O Status (IO)
OFF No power or outputs off
Flashing GRN/OFF Idle/program mode - one or more I/O modules in Idle Mode
Solid GRN Device operational - all I/O modules in Run Mode
Flashing RED/OFF Recoverable fault - one or more I/O modules may be in Fault Mode
Solid RED Unrecoverable fault - one or more I/O modules may be in Fault Mode
Diagnostic Status (DIAG)
OFF No power or no diagnostics running
Flashing Amber Main Program detected an error - number of flashes indicates the error
Flashing Green/OFF Diagnostic self-tests are in progress
Flashing RED/OFF Diagnostics found error - number of flashes indicates which test failed
One flash- RAM test failed
Two flashes- Boot program checksum failed
Three flashes- Main program checksum failed
Four flashes- Configuration checksum failed
Five flashes- Access to program or configuration failed
Six flashes - Backplane power fault (Series B only)
Solid RED Watchdog tripped
Status Indicators Meaning