Rockwell-automation 1769-ADN Compact I/O 1769-ADN DeviceNet Adapter Manuel d'utilisateur Page 80

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 204
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 79
Publication 1769-UM001B-EN-P - October 2002
4-4 Configuring Your Compact I/O Series B DeviceNet Adapter
Follow these steps to assign banks to each module:
a. Select the desired module and choose Properties.
You’ll see a screen similar to this.
b. Enter the bank number in the Bank field.
c. Choose OK.
Note: A second I/O bank may be necessary if your bank 1
power supply has an insufficient power budget for the I/O
modules required for your application.
Note: Make sure your bank-to-bank expansion cable (e.g.
1769-CR1) is in the last (right-most) component of bank 1.
TIP
To save time, assign the bank numbers to the
first (left-most) modules in each bank, starting
with bank one. The software ripples the bank
modification down the list when you choose
OK.
Vue de la page 79
1 2 ... 75 76 77 78 79 80 81 82 83 84 85 ... 203 204

Commentaires sur ces manuels

Pas de commentaire