Rockwell-automation 1762-IQ8OW6 DC-Input/Relay-Output Combination Modu Manuel d'utilisateur Page 9

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 20
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 8
DC-Input/Relay-Output Combination Module 9
Publication 1762-IN018B-EN-P - July 2013
Ground the DC-Input/Relay-Output Combination Module
This product is intended to be mounted to a well-grounded mounting surface such as a metal
panel. Additional grounding connections from the module’s mounting tabs or DIN rail (if used)
are not required unless the mounting surface cannot be grounded. Refer to Industrial
Automation Wiring and Grounding Guidelines, Allen-Bradley publication
1770-4.1, for
additional information.
Wire the Finger-safe Terminal Block
When wiring the terminal block, keep the finger-safe cover in place.
1. Route the wire under the terminal pressure plate.
You can use the stripped end of the wire or a spade lug. The terminals will accept a
6.35 mm (0.25 in.) spade lug.
2. Tighten the terminal screw making sure the pressure plate secures the wire.
Recommended torque when tightening terminal screws is 0.90 Nm (8 lb-in.).
ATTENTION
Miswiring of the module to an AC power source will damage the module.
Vue de la page 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 ... 19 20

Commentaires sur ces manuels

Pas de commentaire