Rockwell-automation 1747-PCINT API Software for 1746 I/O Manuel d'utilisateur Page 12

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 155
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 11
1–4 Overview
Publication 1747-6.5.3 June 1998
Your application (the code you develop using the API) uses the dual port memory
to communicate with the scanner to handle control functions on the 1746 backplane,
such as:
scanner commands and responses
battery and scanner status
scan rate frequency and timing
I/O image counters
priority messages and interrupts
semaphores to ensure data integrity
software-generated watchdogs
control of the 4 user-definable LEDs, the 2-position jumper, and the 3-
position switch
The scanner functionality of the dual port supports I/O control functions, such as:
synchronizing scans to the application
forcing I/O
defining discrete-input interrupts
defining I/O module-driven interrupts (such as for the 1746-BAS module)
enabling and disabling I/O slots
resetting I/O
In addition to providing access to the control scanner, the dual port memory also
provides non-volatile (optional battery-backed) storage for:
I/O values
application parameters (timers, counters, presets)
Scanner Modes The scanner CPU operates in six basic modes:
performing POST (power-on self test)
waiting for host initialization
Idle
Scan
Faulted
non-recoverable fault
After the scanner successfully completes the POST, the scanner waits for an
initialization complete command from the application. Once the scanner receives
this command, the scanner enters Idle mode.
Before the scanner can enter Scan mode, the application must download a valid
I/O configuration to the scanner.
If a recoverable fault occurs, the scanner enters Faulted mode. Use the
OC_ClearFault API function to clear the fault before the scanner can resume
operating in Scan mode.
Vue de la page 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 154 155

Commentaires sur ces manuels

Pas de commentaire