18
SLC 500 Analog Input Module
Publication 1746-IN006A-US-P
Physical Specifications
Environmental Specifications
Description Specification
LED Indicators 9 green status indicators
one for each of 8 channels and one for module status
Module ID Code Class 1 Interface: 3526
Class 3 Interface: 12726
Recommended Cable Belden #8761 or equivalent
Maximum Wire Size Two 14 AWG wires per terminal
Maximum Cable
Impedance
Voltage Source (with less than 10
impedance):
40
maximum loop impedance, for <1LSB error
Current Source (transmitter properly wired to its power supply):
250
maximum loop impedance, to meet common-mode voltage
requirements
Terminal Block Removable, Allen-Bradley spare part Catalog Number 1746-RT25G
Description Specification
Operating Temperature 0°C to +55°C (32°F to 133°F) in any slot except 0
0°C to 60°C (32°F to 140°F) in right most slot of chassis
Storage Temperature
-40
°
C to
+
85
°
C (-40
°
F to
+
185
°
F)
Relative Humidity 5% to 95% (without condensation)
Agency Certification UL listed
CSA approved
CE compliant for all applicable directives
Hazardous Environment
Classification
Class 1 Division 2 Hazardous Environment