2 POINTBlock ac 8 Input/8 Output Module
Publication 1734-5.22 - February 2000
ATTENTION
!
Whatever field power you supply is connected to
the internal field-power bus. For example, if
120V ac is applied to the power connections,
there will be 120V ac applied to the modules
through the internal field-power bus.
POINT I/O modules to the right of the module
will also have that internal power bus voltage
applied, unless you use a 1734-FPD to interrupt
and change the field power-bus voltage.
CH
SH
24
CL
RT
En
CH
CL
GND
5V
DeviceNet
Connector
PointBus Expansion Port
(allows expansion of up to
12 POINT I/O modules)
Field Bus
Connector
24V
to 5V
Microprocessor
I/O Circuits
I/O Connections
Power
Connections
41971
120V ac