42 Calibrate Your Module
4. From the Device Parameters dialog, select Calibration at the Groups
pull-down.
Input (mV) Calibration
Before calibrating the module you need to select the sensor type and download
it to the module.
Perform the following procedure from the Device Parameters dialog.
This is the Groups pull-down.
IMPORTANT
Apply power to the power supply and module for at least 10
minutes before calibrating the module.
Delete all I/O connections by removing the module from its
master's scan list and inhibiting the module in RSLogix. When
there is no connection present the Network Status Indicator
should flash green.