Rockwell-automation 1734-ADN, ADNX Point I/O DeviceNet Adapter Install Manuel d'utilisateur Page 21

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 28
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 20
POINT I/O DeviceNet Adapter 21
Publication
1734-IN026A-EN-P - April 2005
Specifications
Communication Interface Specifications
DeviceNet Communication Rate 125K bit/s (500m maximum)
250K bit/s (250m maximum)
500K bit/s (100m maximum)
DeviceNet Cable Allen-Bradley part number 1485C-P1-Cxxx
Refer to publication NETS-SG001 for more information.
Module Location Starter module - left side of 1734 system
Number of Powered Modules 63 maximum
Number of Integrated I/O
Channels
0
Number of I/O Points, Max. 504
DeviceNet Nodes with
Maximum I/O, Total
1
Node Address 1
I/O Module Capacity 63
DeviceNet Current 30mA
POINTBus Current 1000mA @5V dc +
5% (4.75...5.25V)