Rockwell-automation 1503VC IntelliVAC Plus Contactor Control Module Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Équipement Rockwell-automation 1503VC IntelliVAC Plus Contactor Control Module. Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 387
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs

Résumé du contenu

Page 1 - Control Module

IntelliVAC™ Plus ContactorControl ModuleBulletin 1503VCUser Manual

Page 2 - Important User Information

viii Table of Contents 1503-UM054C-EN-P – June 2013

Page 3 - Table of Contents

Chapter 7 1503-UM054C-EN-P – June 2013 Communications The communications systems implemented within the IntelliVAC Plus product can be divided in

Page 4

7-2 Communications 1503-UM054C-EN-P – June 2013 the RS485 interface, for both the IntelliVAC Base and IntelliVAC Enhanced modules. This inte

Page 5

Communications 7-3 1503-UM054C-EN-P – June 2013 If AutoBaud is enabled then the DNet Baud that was selected will be overridden with the

Page 6 - Chapter 8 Configurations

7-4 Communications 1503-UM054C-EN-P – June 2013 DeviceNet Profile The IntelliVAC Plus is defined within the “miscellaneous device” object c

Page 7 - Chapter 9 DeviceLogix

Communications 7-5 1503-UM054C-EN-P – June 2013 Hold State In general when the hold state option is selected the unit will continue to

Page 8

7-6 Communications 1503-UM054C-EN-P – June 2013 Mask HIM/PC Logic mask 3 is considered a test and diagnostic state. As such if network comm

Page 9

Chapter 8 1503-UM054C-EN-P – June 2013 Configuration/Programming Configuration IB Board DIP Switches Some of the functionality of

Page 10

8-2 Configuration/Programming 1503-UM054C-EN-P – June 2013 This set of switches defines the amount of time, after an OPEN

Page 11 - Product Description

Configuration/Programming 8-3 1503-UM054C-EN-P – June 2013 Contactor Type This set of switches defines the type of vacuum contactor that is

Page 12 - Description

8-4 Configuration/Programming 1503-UM054C-EN-P – June 2013 Time Delay Undervoltage Configuration (TDUV) This setting controls the amount of

Page 13

Chapter 1 1503-UM054C-EN-P –June 2013 Product Description Introduction This document contains information for the Allen-Bradley Bulletin 150

Page 14 - TOP VIEW

Configuration/Programming 8-5 1503-UM054C-EN-P – June 2013 This function is useful for applications that require a contactor to re-close aft

Page 15 - Versions

8-6 Configuration/Programming 1503-UM054C-EN-P – June 2013 MC RS485 Addressing This set of DIP switches defines the RS485 address of the Int

Page 16 - I M P O R T A N T

Configuration/Programming 8-7 1503-UM054C-EN-P – June 2013 Table 8.K – Termination Resistor Installation in IntelliVAC MC System Units in MC

Page 17

8-8 Configuration/Programming 1503-UM054C-EN-P – June 2013 Programming the IntelliVAC Base Module The IntelliVAC base module firmware is up

Page 18

Configuration/Programming 8-9 1503-UM054C-EN-P – June 2013  Move the application disable jumper to the “Program” position as noted on th

Page 19 - Specifications (cont.)

8-10 Configuration/Programming 1503-UM054C-EN-P – June 2013 Figure 8.5 – IntelliVAC Plus Bootloader Menu  Select the option “Upda

Page 20

Configuration/Programming 8-11 1503-UM054C-EN-P – June 2013 Figure 8.6 – IntelliVAC Base Bootloader Menu The IntelliVAC base bootloade

Page 21

8-12 Configuration/Programming 1503-UM054C-EN-P – June 2013 Figure 8.7 – IntelliVAC Base Programming Completed Upload New Firmware Th

Page 22 - Receiving and Storage

Configuration/Programming 8-13 1503-UM054C-EN-P – June 2013 Figure 8.8 - Upload new firmware prompt and send file dialog box After sele

Page 23 - 2-2 Receiving and Storage

8-14 Configuration/Programming 1503-UM054C-EN-P – June 2013 Upon completion of the transfer the transfer dialog box will disappear. The CRC

Page 24 - Installation

1-2 Product Description 1503-UM054C-EN-P –June 2013 Description IntelliVAC Plus is an efficient and flexible solution for controlling me

Page 25 - 3-2 Installation

Configuration/Programming 8-15 1503-UM054C-EN-P – June 2013 Updating the IntelliVAC Plus using Control Flash In order to update the firmwar

Page 26 - Installation 3-3

8-16 Configuration/Programming 1503-UM054C-EN-P – June 2013 Figure 8.12 - Select IntelliVAC Plus in Control Flash • After selecting “OK

Page 27

Configuration/Programming 8-17 1503-UM054C-EN-P – June 2013 Figure 8.13 Firmware Update Complete I M P O R T A N TI M P O R T A N T It wil

Page 28 - Description of Features

8-18 Configuration/Programming 1503-UM054C-EN-P – June 2013

Page 29

Chapter 9 1503-UM054C-EN-P – June 2013 DeviceLogix DLX – DeviceLogix refers to the integrated logic capability of the IntelliVAC Plus . IE

Page 30

9-2 DeviceLogix 1503-UM054C-EN-P – June 2013 Direct Commands Direct commands are specific commands such as 'open contactor 1' or &

Page 31 - Contactor Close

DeviceLogix 9-3 1503-UM054C-EN-P – June 2013 DeviceLogix What is DeviceLogix DeviceLogix functionality has been added to

Page 32 - Features

9-4 DeviceLogix 1503-UM054C-EN-P – June 2013 • Device Input – A physical input of the device. Device inputs represent the actual inputs, s

Page 33 - Delayed Restart (General)

DeviceLogix 9-5 1503-UM054C-EN-P – June 2013 A connection (wire) between function blocks is defined when an input pin of one function

Page 34 - Temporary Jog Function

9-6 DeviceLogix 1503-UM054C-EN-P – June 2013 Launching the DeviceLogix Editor After you configure the properties for the IntelliVAC Plus,

Page 35

Product Description 1-3 1503-UM054C-EN-P – June 2013 Figure 1.3 – IntelliVAC Plus Base Model

Page 36 - Time Stamp

DeviceLogix 9-7 1503-UM054C-EN-P – June 2013 Selection Dialog, you are prompted to select the editor type that you want to launch. Selec

Page 37 -

9-8 DeviceLogix 1503-UM054C-EN-P – June 2013 Figure 9.2 – Select Logic Editor Type I M P O R T A N TI M P O R T A N T The IntelliVAC P

Page 38

DeviceLogix 9-9 1503-UM054C-EN-P – June 2013 1. Upload Logic To upload logic click the Upload Logic icon or alternatively select Com

Page 39

9-10 DeviceLogix 1503-UM054C-EN-P – June 2013 6. Verify Logic To verify the logic’s syntax, click the Verify icon in the standard toolbar

Page 40

DeviceLogix 9-11 1503-UM054C-EN-P – June 2013 DeviceLogix Function Block Elements Function block elements consist of: • I/O compon

Page 41 - Valid Data Range

9-12 DeviceLogix 1503-UM054C-EN-P – June 2013 Digital Output Point (DOP) The following kinds of digital outputs are supported: • Physic

Page 42

DeviceLogix 9-13 1503-UM054C-EN-P – June 2013

Page 43 - Contactors)

9-14 DeviceLogix 1503-UM054C-EN-P – June 2013 Boolean Function Blocks The following truth table describe the boolean function blocks by list

Page 44

DeviceLogix 9-15 1503-UM054C-EN-P – June 2013 Table 9.C – Bistable Function Block Output Table Function Reset Input (Set) Output Val

Page 45

9-16 DeviceLogix 1503-UM054C-EN-P – June 2013 timer resets the output to FALSE the pulse timer can again trigger the process by sensing a FALS

Page 46

1-4 Product Description 1503-UM054C-EN-P –June 2013 Description (cont.) BASE MODULEIntelliVAC MODULE I/OTOP VIEWCUSTOMER I/OMCBASE CONNECTOR

Page 47

DeviceLogix 9-17 1503-UM054C-EN-P – June 2013 If the timer senses a TRUE level on the RESET input at any time during the operation of

Page 48 - Power Fail Operation

9-18 DeviceLogix 1503-UM054C-EN-P – June 2013 output remains TRUE, and the accumulator is cleared, essentially ignoring the input. If the tim

Page 49 - Status Display Items

DeviceLogix 9-19 1503-UM054C-EN-P – June 2013 Figure 9.9 – Timing Diagram for the Counter Function with a Preset Value = 3 Table

Page 50

9-20 DeviceLogix 1503-UM054C-EN-P – June 2013 Figure 9.10 – Timing Diagram for the Up/Down Counter with a Preset Value = 3 Table

Page 51

DeviceLogix 9-21 1503-UM054C-EN-P – June 2013 • Clear Latched hardware faults Go Online Once you’ve created your logic and set up you

Page 52

9-22 DeviceLogix 1503-UM054C-EN-P – June 2013 Figure 9.11 – Modify Function Block Attributes In order to change a value: 1. Double-

Page 53

DeviceLogix 9-23 1503-UM054C-EN-P – June 2013 1. Select Tools>Edit so that a check mark appears on the menu, indicating that you

Page 54 - Contactor Fails to Pick Up

9-24 DeviceLogix 1503-UM054C-EN-P – June 2013 Add a digital output point (DOP) In order to add an output tab click the “Bit Output” button.

Page 55

DeviceLogix 9-25 1503-UM054C-EN-P – June 2013 Note: A double arrow will appear on the connection for which data has been assumed avai

Page 56

9-26 DeviceLogix 1503-UM054C-EN-P – June 2013 To apply forces, right click on the input or output element you wish to force. A pop-up appea

Page 57

Product Description 1-5 1503-UM054C-EN-P – June 2013  A wide range of supply voltage (110 – 240 V AC 50/60Hz, 110 - 250 V DC) all

Page 58

DeviceLogix 9-27 1503-UM054C-EN-P – June 2013 Figure 9.16 – Input Forced Indication Forcing Outputs The following list describes

Page 59 - Status LEDs

9-28 DeviceLogix 1503-UM054C-EN-P – June 2013 Figure 9.18 – Dual Function Bit Behavior In Figure 9.18, the “Stop” output tag is connect

Page 60

DeviceLogix 9-29 1503-UM054C-EN-P – June 2013 Customized Logic Mode: This mode allows the user to freely create control logic using al

Page 61

9-30 DeviceLogix 1503-UM054C-EN-P – June 2013 IBX-Input2 This bit represents the status of the corresponding “open” input on the IntelliVAC

Page 62

DeviceLogix 9-31 1503-UM054C-EN-P – June 2013 JOG This is a dual function bit which can be used to represent the status of a “JOG” pus

Page 63

9-32 DeviceLogix 1503-UM054C-EN-P – June 2013 Test Mode Status This is a dual function bit which can be used to describe the status of a sel

Page 64 - DeviceNet Power Loss

DeviceLogix 9-33 1503-UM054C-EN-P – June 2013 IBX-Mechanical latch Fail to Trip This is a fault bit which only applies to a mechanica

Page 65

9-34 DeviceLogix 1503-UM054C-EN-P – June 2013 IBX-Under voltage with close command present This is a warning bit which will be set when the

Page 66

DeviceLogix 9-35 1503-UM054C-EN-P – June 2013 Output bits/tags Hardware Boolean Outputs Net out A This bit controls the status of

Page 67 - (DeviceNet)

9-36 DeviceLogix 1503-UM054C-EN-P – June 2013 Net Out9/Speed SW FWD Status This is the output portion of the Speed SW FWD Status dual functi

Page 68 - (cont.)

1-6 Product Description 1503-UM054C-EN-P –June 2013 circuits to reduce thermal output and decrease sensitivity to leakage current. Refer to

Page 69

DeviceLogix 9-37 1503-UM054C-EN-P – June 2013 This is the output portion of the “Start” dual function bit. Net Out 28/Stop This is the

Page 70

9-38 DeviceLogix 1503-UM054C-EN-P – June 2013 This is an example of a basic logical replacement for a typical relay control circuit. Pushin

Page 71

DeviceLogix 9-39 1503-UM054C-EN-P – June 2013 After selecting the desired control program the IntelliVAC Plus module must be reset to

Page 72

9-40 DeviceLogix 1503-UM054C-EN-P – June 2013

Page 73

Chapter 10 1503-UM054C-EN-P – June 2013 Troubleshooting IB Operational Troubleshooting Procedures The following table identifies possible causes

Page 74

10-2 Troubleshooting 1503-UM054C-EN-P – June 2013 Table 10.A – IB Operational Troubleshooting Procedures (cont.) LED Color State Condition/P

Page 75 - Input LEDs

Troubleshooting 10-3 1503-UM054C-EN-P – June 2013 Table 10.A – IB Operational Troubleshooting Procedures (cont.) LED Color State Condi

Page 76 - IntelliVAC Plus Basic Wiring

10-4 Troubleshooting 1503-UM054C-EN-P – June 2013 Table 10.A – IB Operational Troubleshooting Procedures (cont.) LED Color State Condition/P

Page 77 - Ground Connection

Troubleshooting 10-5 1503-UM054C-EN-P – June 2013 Table 10.B - IE Operations Troubleshooting Procedures (cont.) Plus Status LED Color

Page 78 - EX. CAP

10-6 Troubleshooting 1503-UM054C-EN-P – June 2013 Table 10.B - IE Operations Troubleshooting Procedures (cont.) Plus Status LED Color State

Page 79 - Contactors

Product Description 1-7 1503-UM054C-EN-P – June 2013 For further information regarding programming of firmware see Chapter 8 “Configurati

Page 80 - Three-Wire Control

Troubleshooting 10-7 1503-UM054C-EN-P – June 2013 Table 10.B - IE Operations Troubleshooting Procedures (cont.) Plus Status LED Color

Page 81 - Contactors (cont.)

10-8 Troubleshooting 1503-UM054C-EN-P – June 2013 Table 10.C – IE Operational Trouble Shooting Procedures (cont.) 7-Segment Display State Co

Page 82 - Mechanical Latch

Troubleshooting 10-9 1503-UM054C-EN-P – June 2013 Table 10.C – IE Operational Trouble Shooting Procedures (cont.) 7-Segment Display Sta

Page 83 - Capacitor Trip

10-10 Troubleshooting 1503-UM054C-EN-P – June 2013 Table 10.D – MC Operational Troubleshooting Procedures 7-Segment Display State Condition/

Page 84

Appendix A 1503-UM054C-EN-P – June 2013 Fuse Protection Introduction The IntelliVAC module requires external fuse protection to coordinate wi

Page 85

A-2 Fuse Protection 1503-UM054C-EN-P – June 2013

Page 86

Appendix B 1503-UM054C-EN-P – June 2013 Parameters Introduction This section provides a detailed description of the parameters used in the c

Page 87

B-2 Parameters 1503-UM054C-EN-P – June 2013 Table B.1 – Status Word for IB1 Bit Enum Text Description 0 Bit 0: unused unused 1 Bit 1: unused

Page 88 - Wiring

Parameters B-3 1503-UM054C-EN-P – June 2013 Table B.3 – Conversion Table Binary Hex Binary Hex Binary Hex Binary Hex 0000 0 0100 4

Page 89 - 6-2 Wiring (MC)

B-4 Parameters 1503-UM054C-EN-P – June 2013 Auxiliary Input Status from IntelliVAC Base Unit #2 [IB 2 Module Aux. Status] Parameter Number: 2

Page 90 - Wiring (MC) 6-3

1-8 Product Description 1503-UM054C-EN-P –June 2013 Through RSNetWorx, IntelliVAC Plus firmware version can be viewed in device general page

Page 91 - 6-4 Wiring (MC)

Parameters B-5 1503-UM054C-EN-P – June 2013 Auxiliary Input Status from IntelliVAC Base Unit #4 [IB 4 Module Aux. Status] Parameter Numbe

Page 92 - Wiring (MC) 6-5

B-6 Parameters 1503-UM054C-EN-P – June 2013 Close Input Status from IntelliVAC Base Unit #1 [IB 1 Module Close Status] Parameter Number: 6,5,

Page 93 - 6-6 Wiring (MC)

Parameters B-7 1503-UM054C-EN-P – June 2013 Close Input Status from IntelliVAC Base Unit #3 [IB 3 Module Close Status] Parameter Number:

Page 94 - Wiring (MC) 6-7

B-8 Parameters 1503-UM054C-EN-P – June 2013 Close Input Status from IntelliVAC Base Unit #5 [IB 5 Module Close Status] Parameter Number: 10,_

Page 95 - 6-8 Wiring (MC)

Parameters B-9 1503-UM054C-EN-P – June 2013 Open Input Status from IntelliVAC Base Unit #2 [IB 2 Module Open Status] Parameter Number:

Page 96 - Transition Timer

B-10 Parameters 1503-UM054C-EN-P – June 2013 Open Input Status from IntelliVAC Base Unit #4 [IB 4 Module Open Status] Parameter Number: 14,12

Page 97 - 6-10 Wiring (MC)

Parameters B-11 1503-UM054C-EN-P – June 2013 Close Coil Command for IntelliVAC Base Unit #1 [IB 1 Close Coil Command] Parameter Number:

Page 98

B-12 Parameters 1503-UM054C-EN-P – June 2013 Close Coil Command for IntelliVAC Base Unit #3 [IB 3 Close Coil Command] Parameter Number: 18,15

Page 99 - 6-12 Wiring (MC)

Parameters B-13 1503-UM054C-EN-P – June 2013 Close Coil Command for IntelliVAC Base Unit #5 [IB 5 Close Coil Command] Parameter Number:

Page 100 - Communications

B-14 Parameters 1503-UM054C-EN-P – June 2013 Trip Coil Command for IntelliVAC Base Unit #2 [IB 2 Trip Coil Command] Parameter Number: 22,18,1

Page 101 - DeviceNet

Product Description 1-9 1503-UM054C-EN-P – June 2013 Specifications (cont.) Table 1.B – Electrical Ratings Main Input Voltage (L1 to L2/

Page 102 - DeviceNet MACID

Parameters B-15 1503-UM054C-EN-P – June 2013 Trip Coil Command for IntelliVAC Base Unit #4 [IB 4 Trip Coil Command] Parameter Number:

Page 103 - 7-4 Communications

B-16 Parameters 1503-UM054C-EN-P – June 2013 Contactor Relay Status for IntelliVAC Base Unit #1 [IB 1 Contactor Status Relay Status] Parameter

Page 104 - Communications 7-5

Parameters B-17 1503-UM054C-EN-P – June 2013 Contactor Relay Status for IntelliVAC Base Unit #3 [IB 3 Contactor Status Relay Status] Para

Page 105 - 7-6 Communications

B-18 Parameters 1503-UM054C-EN-P – June 2013 Contactor Relay Status for IntelliVAC Base Unit #5 [IB 5 Contactor Status Relay Status] Parameter

Page 106 - Configuration/Programming

Parameters B-19 1503-UM054C-EN-P – June 2013 Module Status Relay Status for IntelliVAC Base Unit #2 [IB 2 Module Status Relay Status] Par

Page 107 - Out Time

B-20 Parameters 1503-UM054C-EN-P – June 2013 Module Status Relay Status for IntelliVAC Base Unit #4 [IB 4 Module Status Relay Status] Parameter

Page 108 - Table 8.C – Contactor Type

Parameters B-21 1503-UM054C-EN-P – June 2013 Close Coil Current for IntelliVAC Base Unit #1 [IB 1 Close Current] Parameter Number: 36,2

Page 109

B-22 Parameters 1503-UM054C-EN-P – June 2013 Close Coil Current for IntelliVAC Base Unit #3 [IB 3 Close Current] Parameter Number: 38,31,24,_

Page 110 - Table 8.G – Future Use

Parameters B-23 1503-UM054C-EN-P – June 2013 Close Coil Current for IntelliVAC Base Unit #5 [IB 5 Close Current] Parameter Number: 40_,

Page 111 - TERMINATION

B-24 Parameters 1503-UM054C-EN-P – June 2013 Hold Coil Current for IntelliVAC Base Unit #2 [IB 2 Hold Current] Parameter Number: 42,34,26,18,

Page 112 - Programming

Important User InformationRead this document and the documents listed in the Additional Resources section about installation, configuration, and opera

Page 113 -  Power down the unit

1-10 Product Description 1503-UM054C-EN-P –June 2013 5.1 (0.20)Dimensions in mm (inches)29.7(1.17)174.8(6.88)185.3(7.29)59.4(2.34)165.9 (6.53)5

Page 114

Parameters B-25 1503-UM054C-EN-P – June 2013 Hold Coil Current for IntelliVAC Base Unit #4 [IB 4 Hold Current] Parameter Number: 44,36,

Page 115

B-26 Parameters 1503-UM054C-EN-P – June 2013 Trip Coil Current for IntelliVAC Base Unit #1 [IB 1 Trip Current] Parameter Number: 46,37,28,19,

Page 116

Parameters B-27 1503-UM054C-EN-P – June 2013 Trip Coil Current for IntelliVAC Base Unit #3 [IB 3 Trip Current] Parameter Number: 48,39,

Page 117 -  Select “send”

B-28 Parameters 1503-UM054C-EN-P – June 2013 Trip Coil Current for IntelliVAC Base Unit #5 [IB 5 Trip Current] Parameter Number: 50,_,_,_,_.

Page 118

Parameters B-29 1503-UM054C-EN-P – June 2013 Input Line Voltage for IntelliVAC Base Unit #2 [IB 2 Line Voltage] Parameter Number: 52,42

Page 119

B-30 Parameters 1503-UM054C-EN-P – June 2013 Input Line Voltage for IntelliVAC Base Unit #4 [IB 4 Line Voltage] Parameter Number: 54,44,_,_,_

Page 120

Parameters B-31 1503-UM054C-EN-P – June 2013 DC Bus Voltage for IntelliVAC Base Unit #1 [IB 1 DC Bus Voltage] Parameter Number: 56,45,3

Page 121

B-32 Parameters 1503-UM054C-EN-P – June 2013 DC Bus Voltage for IntelliVAC Base Unit #3 [IB 3 DC Bus Voltage] Parameter Number: 58,47,36,_,_.

Page 122 - IE/IB Firmware Revisions

Parameters B-33 1503-UM054C-EN-P – June 2013 DC Bus Voltage for IntelliVAC Base Unit #5 [IB 5 DC Bus Voltage] Parameter Number: 60,_,_,

Page 123

B-34 Parameters 1503-UM054C-EN-P – June 2013 Enhanced Module Hardware Output State [IE Hardware Outputs] Parameter Number: 62,50,38,26,14. Ac

Page 124 - DeviceLogix

Product Description 1-11 1503-UM054C-EN-P – June 2013

Page 125 - 9-2 DeviceLogix

Parameters B-35 1503-UM054C-EN-P – June 2013 DeviceNet Voltage [24V DeviceNet Voltage] Parameter Number: 64,52,40,28,16. Access rule:

Page 126 - Input and Output Bits

B-36 Parameters 1503-UM054C-EN-P – June 2013 Table B.6 – DeviceLogix Programs Bit Enum Text Description 0 User customized DeviceLogix Prog. Cu

Page 127 - Local Function Block Logic

Parameters B-37 1503-UM054C-EN-P – June 2013 IntelliVAC Plus Action on Loss of DeviceNet Communications [Loss Communication Action] Parame

Page 128 - DeviceLogix Operating Modes

B-38 Parameters 1503-UM054C-EN-P – June 2013 Table B.8 – Consumed Network Bits Bit Enum Text Description 0 Consumed Network Bit 0 Status of C

Page 129 - 9-6 DeviceLogix

Parameters B-39 1503-UM054C-EN-P – June 2013 Produced Network Bits [Produced Network Bits] Parameter Number: 71,59,47,35,22. Access rule

Page 130 - DeviceLogix 9-7

B-40 Parameters 1503-UM054C-EN-P – June 2013 Discrete Output Point Fault Action [DOP Fault Action] Parameter Number: 72,60,48,36,23. Access ru

Page 131 - 9-8 DeviceLogix

Parameters B-41 1503-UM054C-EN-P – June 2013 Discrete Output Point Idle Value [DOP Idle Value] Parameter Number: 75,63,51,34,26. Access

Page 132 - DeviceLogix 9-9

B-42 Parameters 1503-UM054C-EN-P – June 2013 DeviceNet Media Access Carrier Identification [DNet MAC ID] Parameter Number: 77,65,53,41,28. Ac

Page 133 - 9-10 DeviceLogix

Parameters B-43 1503-UM054C-EN-P – June 2013 Enabling of the AutoBaud Rate Feature [Autobaud Enable] Parameter Number: 79,67,55,43,30. A

Page 134

B-44 Parameters 1503-UM054C-EN-P – June 2013 Status of the Change Of State Mask [Status COS Mask] Parameter Number: 82,70,58,46,33. Access rul

Page 135 - 9-12 DeviceLogix

Chapter 2 1503-UM054C-EN-P – June 2013 Receiving and Storage Receiving Upon receiving the controller, remove the packing and check for damag

Page 136 - DeviceLogix 9-13

Parameters B-45 1503-UM054C-EN-P – June 2013 Status of the Change Of State Mask [Set to Defaults] Parameter Number: 83,71,59,47,34. Acce

Page 137

B-46 Parameters 1503-UM054C-EN-P – June 2013 Selects the Format of the I/O Data Consumed [Consumed IO Assy] Parameter Number: 84,72,60,48,35.

Page 138 - Pulse Timer

Parameters B-47 1503-UM054C-EN-P – June 2013 Table B.14 – Format of I/O Data Produced Value Enum Text Description 10 Default Produced As

Page 139 - On Delay Timer

B-48 Parameters 1503-UM054C-EN-P – June 2013 Table B.15 – Network Output COS Mask Definition (cont.) Bit Enum Text Description Action 10 Net

Page 140

Parameters B-49 1503-UM054C-EN-P – June 2013 Configuration Parameters Altitude Above Sea Level [Altitude] Parameter Number: 87,7

Page 141

B-50 Parameters 1503-UM054C-EN-P – June 2013 Real Time Clock Time [RTC Time] Parameter Number: 89,77,65,53,40. Access rule: Get/Set Data Ty

Page 142

Parameters B-51 1503-UM054C-EN-P – June 2013 Table B.17 – RTC World Time Zone Selection Local (cont.) Value Enum Text Description 13 GM

Page 143

B-52 Parameters 1503-UM054C-EN-P – June 2013 Override the Loss of an IO Connection [Comm Override] Parameter Number: 92,80,68,56,43. Access ru

Page 144 - Go Online

Parameters B-53 1503-UM054C-EN-P – June 2013 Type of Contactor Selected for IB2 [IB 2 Contactor Type] Parameter Number: 94,82,70,58,_. A

Page 145

B-54 Parameters 1503-UM054C-EN-P – June 2013 Type of Contactor Selected for IB4 [IB 4 Contactor Type] Parameter Number: 96,84,_,_,_. Access ru

Page 146 - The Editor

2-2 Receiving and Storage 1503-UM054C-EN-P – June 2013

Page 147 - Assume Data Available

Parameters B-55 1503-UM054C-EN-P – June 2013 Time Delay UnderVoltage Setting for IB1 [IB 1 TDUV Configure] Parameter Number: 98,85,72,5

Page 148

B-56 Parameters 1503-UM054C-EN-P – June 2013 Time Delay UnderVoltage Setting for IB3 [IB 3 TDUV Configure] Parameter Number: 100,87,74,_,_. A

Page 149 - Table 9.I – Input Forcing

Parameters B-57 1503-UM054C-EN-P – June 2013 Time Delay UnderVoltage Setting for IB5 [IB 5 TDUV Configure] Parameter Number: 102,_,_,_,

Page 150 - Table 9.J – Output Forcing

B-58 Parameters 1503-UM054C-EN-P – June 2013 Power-Up Safety Setting for IB2 [IB 2 Power-Up Safety Setting] Parameter Number: 104,90,76,62,_.

Page 151 - 9-28 DeviceLogix

Parameters B-59 1503-UM054C-EN-P – June 2013 Power-Up Safety Setting for IB4 [IB 4 Power-Up Safety Setting] Parameter Number: 106,92,_,

Page 152

B-60 Parameters 1503-UM054C-EN-P – June 2013 Learn Mode Setting From IB1 [IB 1 Learn Mode Setting] Parameter Number: 108,93,78,63,47. Access

Page 153

Parameters B-61 1503-UM054C-EN-P – June 2013 Learn Mode Setting From IB3 [IB 3 Learn Mode Setting] Parameter Number: 110,95,80,_,_. Acc

Page 154

B-62 Parameters 1503-UM054C-EN-P – June 2013 Learn Mode Setting From IB5 [IB 5 Learn Mode Setting] Parameter Number: 112,_,_,_,_. Access rule

Page 155

Parameters B-63 1503-UM054C-EN-P – June 2013 Drop Out Time Setting for IB2 [IB 2 Drop Out Time] Parameter Number: 114,98,82,66,_. Acces

Page 156

B-64 Parameters 1503-UM054C-EN-P – June 2013 Drop Out Time Setting for IB4 [IB 4 Drop Out Time] Parameter Number: 116,100,_,_,_. Access rule:

Page 157 - Network Boolean Inputs

Chapter 3 1503-UM054C-EN-P – June 2013 Installation General Precautions In addition to the precautions listed throughout this manual, th

Page 158 - Network Boolean Outputs

Parameters B-65 1503-UM054C-EN-P – June 2013 Drop Out Time Setting From IB1 DIP Switches [IB 1 Drop Out Time DIP Setting] Parameter Numbe

Page 159

B-66 Parameters 1503-UM054C-EN-P – June 2013 Table B.24 – Drop Out Time Settings from IB2 DIP Switches Value Enum Text Description 0 50 ms 50

Page 160 - Simple example

Parameters B-67 1503-UM054C-EN-P – June 2013 Drop Out Time Setting From IB4 DIP Switches [IB 4 Drop Out Time DIP Setting] Parameter Numbe

Page 161

B-68 Parameters 1503-UM054C-EN-P – June 2013 Table B.27 – Drop Out Time Settings From IB5 DIP Switches Value Enum Text Description 0 50 ms 50

Page 162 - DeviceLogix 9-39

Parameters B-69 1503-UM054C-EN-P – June 2013 Contactor Pick Up Time for IB3 [IB 3 Pick Up Time] Parameter Number: 125,107,89,_,_. Acces

Page 163 - 9-40 DeviceLogix

B-70 Parameters 1503-UM054C-EN-P – June 2013 Contactor Pick Up Time for IB5 [IB 5 Pick Up Time] Parameter Number: 127,_,_,_,_. Access rule:

Page 164 - Troubleshooting

Parameters B-71 1503-UM054C-EN-P – June 2013 TDUV Time Setting from IB2 DIP Switches [IB 2 TDUV Time DIP Setting] Parameter Number: 129

Page 165

B-72 Parameters 1503-UM054C-EN-P – June 2013 Table B.30 – TDUV Time Setting From I B3 DIP Switches Value Enum Text Description 0 0.2 Sec 0.2 S

Page 166

Parameters B-73 1503-UM054C-EN-P – June 2013 TDUV Time Setting from IB5 DIP Switches [IB 5 TDUV Time DIP Setting] Parameter Number: 132

Page 167 - Status LED

B-74 Parameters 1503-UM054C-EN-P – June 2013 TDUV Time Setting for IB2 [IB 2 TDUV Time] Parameter Number: 134,114,94,74,_. Access rule: Ge

Page 168

3-2 Installation 1503-UM054C-EN-P – June 2013 Arrangements The IntelliVAC is offered in two arrangements, Integral (part of a Bulletin 1500

Page 169 - 6 pulses

Parameters B-75 1503-UM054C-EN-P – June 2013 TDUV Time Setting for IB4 [IB 4 TDUV Time] Parameter Number: 136,116,_,_,_. Access rule:

Page 170 - 8 pulses

B-76 Parameters 1503-UM054C-EN-P – June 2013 Delay Restart Time for IB1 [IB 1 Delay Restart Time] Parameter Number: 138,117,96,75,53. Access

Page 171

Parameters B-77 1503-UM054C-EN-P – June 2013 Delay Restart Time for IB3 [IB 3 Delay Restart Time] Parameter Number: 140,119,98,_,_. Acc

Page 172 - Segment LED Display

B-78 Parameters 1503-UM054C-EN-P – June 2013 Delay Restart Time for IB5 [IB 5 Delay Restart Time] Parameter Number: 142,_,_,_,_. Access rule:

Page 173

Parameters B-79 1503-UM054C-EN-P – June 2013 Delay Restart Wait Time for IB2 [IB 2 Delay Restart Wait Time] Parameter Number: 144,122,1

Page 174 - Fuse Protection

B-80 Parameters 1503-UM054C-EN-P – June 2013 Delay Restart Wait Time for IB4 [IB 4 Delay Restart Wait Time] Parameter Number: 146,124,_,_,_.

Page 175 - A-2 Fuse Protection

Parameters B-81 1503-UM054C-EN-P – June 2013 Jog Time for IB1 [IB 1 Jog Time] Parameter Number: 148,125,102,79,55. Access rule: Get/S

Page 176 - Parameters

B-82 Parameters 1503-UM054C-EN-P – June 2013 Jog Time for IB3 [IB 3 Jog Time] Parameter Number: 150,127,104,_,_. Access rule: Get/Set Data

Page 177

Parameters B-83 1503-UM054C-EN-P – June 2013 Jog Time for IB5 [IB 5 Jog Time] Parameter Number: 152,_,_,_,_. Access rule: Get/Set Dat

Page 178

B-84 Parameters 1503-UM054C-EN-P – June 2013 Jog Repetition Time for IB2 [IB 2 Jog Repetition Time] Parameter Number: 154,130,106,82,_. Acces

Page 179 - B-4 Parameters

Installation 3-3 1503-UM054C-EN-P – June 2013 Figure 3.2 – Typical Mounting Configurations Note: Adjacent IntelliVAC modules ma

Page 180 - Parameters B-5

Parameters B-85 1503-UM054C-EN-P – June 2013 Jog Repetition Time for IB4 [IB 4 Jog Repetition Time] Parameter Number: 156,132,_,_,_. A

Page 181 - B-6 Parameters

B-86 Parameters 1503-UM054C-EN-P – June 2013 Diagnostics Parameters Invalid Command on IB1 Level [IB 1 Invalid Command] Parameter Number: 15

Page 182 - Parameters B-7

Parameters B-87 1503-UM054C-EN-P – June 2013 Invalid Command on IB3 Level [IB 3 Invalid Command] Parameter Number: 160,135,110,_,_. Ac

Page 183 - B-8 Parameters

B-88 Parameters 1503-UM054C-EN-P – June 2013 Invalid Command on IB5 Level [IB 5 Invalid Command] Parameter Number: 162,_,_,_,_. Access rule:

Page 184 - Parameters B-9

Parameters B-89 1503-UM054C-EN-P – June 2013 Mechanical Latch Fails to Trip on IB2 [IB 2 Mechanical Latch Fail to Trip] Parameter Number

Page 185 - B-10 Parameters

B-90 Parameters 1503-UM054C-EN-P – June 2013 Mechanical Latch Fails to Trip on IB4 [IB 4 Mechanical Latch Fail to Trip] Parameter Number: 16

Page 186 - Parameters B-11

Parameters B-91 1503-UM054C-EN-P – June 2013 Contactor Fails to Pick-Up on IB1 [IB 1 Contactor Fails to Pick-Up] Parameter Number: 168

Page 187 - B-12 Parameters

B-92 Parameters 1503-UM054C-EN-P – June 2013 Contactor Fails to Pick-Up on IB3 [IB 3 Contactor Fails to Pick-Up] Parameter Number: 170,143,1

Page 188 - Parameters B-13

Parameters B-93 1503-UM054C-EN-P – June 2013 Contactor Fails to Pick-Up on IB5 [IB 5 Contactor Fails to Pick-Up] Parameter Number: 172

Page 189 - B-14 Parameters

B-94 Parameters 1503-UM054C-EN-P – June 2013 Contactor Drop-Out during Hold on IB2 [IB 2 Contactor Drop-out During Hold] Parameter Number: 1

Page 190 - Parameters B-15

3-4 Installation 1503-UM054C-EN-P – June 2013 It is recommended the user interface with the IntelliVAC Plus using interposing relays if po

Page 191 - B-16 Parameters

Parameters B-95 1503-UM054C-EN-P – June 2013 Contactor Drop-Out during Hold on IB4 [IB 4 Contactor Drop-out During Hold] Parameter Numbe

Page 192 - Parameters B-17

B-96 Parameters 1503-UM054C-EN-P – June 2013 Contactor Long Drop Out Time on IB1 [IB 1 Contactor Long Drop Out Time] Parameter Number: 178,1

Page 193 - B-18 Parameters

Parameters B-97 1503-UM054C-EN-P – June 2013 Contactor Long Drop Out Time on IB3 [IB 3 Contactor Long Drop Out Time] Parameter Number:

Page 194 - Parameters B-19

B-98 Parameters 1503-UM054C-EN-P – June 2013 Contactor Long Drop Out Time on IB5 [IB 5 Contactor Long Drop Out Time] Parameter Number: 182,_

Page 195 - B-20 Parameters

Parameters B-99 1503-UM054C-EN-P – June 2013 Contactor Fails to Drop Out on IB2 [IB 2 Contactor Fails To Drop Out] Parameter Number: 1

Page 196 - Parameters B-21

B-100 Parameters 1503-UM054C-EN-P – June 2013 Contactor Fails to Drop Out on IB4 [IB 4 Contactor Fails To Drop Out] Parameter Number: 186,15

Page 197 - B-22 Parameters

Parameters B-101 1503-UM054C-EN-P – June 2013 Long Close Time on IB1 [IB 1 Long Close Time] Parameter Number: 188,157,126,95,63. Access

Page 198 - Parameters B-23

B-102 Parameters 1503-UM054C-EN-P – June 2013 Long Close Time on IB3 [IB 3 Long Close Time] Parameter Number: 190,159,128,_,_. Access rule:

Page 199 - B-24 Parameters

Parameters B-103 1503-UM054C-EN-P – June 2013 Long Close Time on IB5 [IB 5 Long Close Time] Parameter Number: 192,_,_,_,_. Access rule:

Page 200 - Parameters B-25

B-104 Parameters 1503-UM054C-EN-P – June 2013 Power Up with Contactor Closed on IB2 [IB 2 Power-up with Contactor Closed] Parameter Number:

Page 201 - B-26 Parameters

Chapter 4 1503-UM054C-EN-P – June 2013 Description of Features The IntelliVAC Plus incorporates a TDUV feature, which will keep the contac

Page 202 - Parameters B-27

Parameters B-105 1503-UM054C-EN-P – June 2013 Power Up with Contactor Closed on IB4 [IB 4 Power-up with Contactor Closed] Parameter Numb

Page 203 - B-28 Parameters

B-106 Parameters 1503-UM054C-EN-P – June 2013 Power Up with Invalid DIP Switch Configuration on IB1 [IB 1 Power-up with Invalid DIP Switch Conf

Page 204 - Parameters B-29

Parameters B-107 1503-UM054C-EN-P – June 2013 Power Up with Invalid DIP Switch Configuration on IB3 [IB 3 Power-up with Invalid DIP Switc

Page 205 - B-30 Parameters

B-108 Parameters 1503-UM054C-EN-P – June 2013 Power Up with Invalid DIP Switch Configuration on IB5 [IB 5 Power-up with Invalid DIP Switch Conf

Page 206 - Parameters B-31

Parameters B-109 1503-UM054C-EN-P – June 2013 Under Voltage with Close Command Present on IB2 [IB 2 U/V with Close Command Present] Para

Page 207 - B-32 Parameters

B-110 Parameters 1503-UM054C-EN-P – June 2013 Under Voltage with Close Command Present on IB4 [IB 4 U/V with Close Command Present] Parameter

Page 208

Parameters B-111 1503-UM054C-EN-P – June 2013 Module not Healthy on IB1 [IB 1 Module not Healthy] Parameter Number: 208,173,138,103,67.

Page 209

B-112 Parameters 1503-UM054C-EN-P – June 2013 Module not Healthy on IB3 [IB 3 Module not Healthy] Parameter Number: 210,175,140,_,_. Access r

Page 210

Parameters B-113 1503-UM054C-EN-P – June 2013 Module not Healthy on IB5 [IB 5 Module not Healthy] Parameter Number: 212,_,_,_,_. Access

Page 211 - Table B.7 – Control Masks

B-114 Parameters 1503-UM054C-EN-P – June 2013 Contactor not Healthy on IB3 [IB 3 Contactor Not Healthy] Parameter Number: 215,179,143,_,_. Acc

Page 212 - Parameters B-37

4-2 Description of Features 1503-UM054C-EN-P – June 2013 TDUV Programmability With the IntelliVAC Plus unit TDUV settings w ill be altered

Page 213

Parameters B-115 1503-UM054C-EN-P – June 2013 Input Line Undervoltage during Close on IB1 [IB 1 Line Undervoltage Close] Parameter Numbe

Page 214

B-116 Parameters 1503-UM054C-EN-P – June 2013 Input Line Undervoltage During Close on IB3 [IB 3 Line Undervoltage Close] Parameter Number: 2

Page 215

Parameters B-117 1503-UM054C-EN-P – June 2013 Input Line Undervoltage during Close on IB5 [IB 5 Line Undervoltage Close] Parameter Numbe

Page 216

B-118 Parameters 1503-UM054C-EN-P – June 2013 Input Line Undervoltage during Hold on IB2 [IB 2 Line Undervoltage Hold] Parameter Number: 224

Page 217 - B-42 Parameters

Parameters B-119 1503-UM054C-EN-P – June 2013 Input Line Undervoltage during Hold on IB4 [IB 4 Line Undervoltage Hold Parameter Number:

Page 218

B-120 Parameters 1503-UM054C-EN-P – June 2013 Input Line Overvoltage on IB1 [IB 1 Line Overvoltage] Parameter Number: 228,189,150,111,71. Acc

Page 219

Parameters B-121 1503-UM054C-EN-P – June 2013 Input Line Overvoltage on IB3 [IB 3 Line Overvoltage] Parameter Number: 230,191,152,_,_.

Page 220

B-122 Parameters 1503-UM054C-EN-P – June 2013 Input Line Overvoltage on IB5 [IB 5 Line Overvoltage] Parameter Number: 232,_,_,_,_. Access ru

Page 221

Parameters B-123 1503-UM054C-EN-P – June 2013 Loss of Input Line Power on IB2 [IB 2 Line Loss] Parameter Number: 234,194,154,114,_. Acce

Page 222

B-124 Parameters 1503-UM054C-EN-P – June 2013 Loss of Input Line Power on IB5 [IB 5 Line Loss] Parameter Number: 237,_,_,_,_. Access rule:

Page 223

Table of Contents 1503-UM054C-EN-P – June 2013 Chapter 1 Product Description Introduction ...

Page 224

Description of Features 4-3 1503-UM054C-EN-P – June 2013  ‘I B1 TDUV time DIP setting = ‘‘0.2’ or ‘0.500’ or ‘1.000’ or ‘2.000’ ‘Sec’

Page 225

Parameters B-125 1503-UM054C-EN-P – June 2013 Main Coil Open on IB3 [IB 3 Main Coil Open] Parameter Number: 240,199,158,_,_. Access rule

Page 226

B-126 Parameters 1503-UM054C-EN-P – June 2013 Trip Coil Open on IB1 [IB 1 Trip Coil Open] Parameter Number: 243,201,159,117,74. Access rule:

Page 227

Parameters B-127 1503-UM054C-EN-P – June 2013 Trip Coil Open on IB4 [IB 4 Trip Coil Open] Parameter Number: 246,204,_,_,_. Access rule:

Page 228

B-128 Parameters 1503-UM054C-EN-P – June 2013 Extended Close Time on IB2 [IB 2 Extended Pick up Time] Parameter Number: 249,206,163,120,_. A

Page 229

Parameters B-129 1503-UM054C-EN-P – June 2013 Extended Close Time on IB4 [IB 4 Extended Pick up Time] Parameter Number: 251,208,_,_,_.

Page 230 - Parameters B-55

B-130 Parameters 1503-UM054C-EN-P – June 2013 Average Number of Operations per Time Unit on IB1 [IB 1 Average Operations per Time Unit] Parame

Page 231 - B-56 Parameters

Parameters B-131 1503-UM054C-EN-P – June 2013 Average Number of Operations per Time Unit on IB2 [IB 2 Average Operations per Time Unit]

Page 232 - Parameters B-57

B-132 Parameters 1503-UM054C-EN-P – June 2013 Average Number of Operations per Time Unit on IB3 [IB 3 Average Operations per Time Unit] Parame

Page 233 - B-58 Parameters

Parameters B-133 1503-UM054C-EN-P – June 2013 Average Number of Operations per Time Unit on IB4 [IB 4 Average Operations per Time Unit]

Page 234 - Parameters B-59

B-134 Parameters 1503-UM054C-EN-P – June 2013 Average Number of Operations per Time Unit on IB5 [IB 5 Average Operations per Time Unit] Parame

Page 235 - B-60 Parameters

4-4 Description of Features 1503-UM054C-EN-P – June 2013  ‘IB1 Drop-Out Time = ‘ ’50 mSec’ to ‘240 mSec’ (resolution is 1mS)  ‘I B2 Drop-

Page 236 - Parameters B-61

Parameters B-135 1503-UM054C-EN-P – June 2013 Total Number of Close Operations on IB1 [IB 1 Master Counter] Parameter Number: 263,217,

Page 237 - B-62 Parameters

B-136 Parameters 1503-UM054C-EN-P – June 2013 Total Number of Close Operations on IB3 [IB 3 Master Counter] Parameter Number: 265,219,173,_,

Page 238 - Parameters B-63

Parameters B-137 1503-UM054C-EN-P – June 2013 Total Number of Close Operations on IB5 [IB 5 Master Counter] Parameter Number: 267,_,_,

Page 239 - B-64 Parameters

B-138 Parameters 1503-UM054C-EN-P – June 2013 highest level will contain the data that was in the second highest level. This system will prov

Page 240

Parameters B-139 1503-UM054C-EN-P – June 2013 Average Number of Operations per Time Unit on IB3 [IB 3 Reset Operations Since Counter] Pa

Page 241

B-140 Parameters 1503-UM054C-EN-P – June 2013 Average Number of Operations per Time Unit on IB4 [IB 4 Reset Operations Since Counter] Paramete

Page 242

Parameters B-141 1503-UM054C-EN-P – June 2013 Average Number of Operations per Time Unit on IB5 [IB 5 Reset Operations Since Counter] Pa

Page 243

B-142 Parameters 1503-UM054C-EN-P – June 2013 Operations since 0 Count Value on IB1 [IB 1 Operations Since 0 Count Value] Parameter Number:

Page 244 - Parameters B-69

Parameters B-143 1503-UM054C-EN-P – June 2013 Time of Operations Since 0 Count Value on IB1 [IB 1 Operations since 0 Time] Parameter Num

Page 245

B-144 Parameters 1503-UM054C-EN-P – June 2013 Date of Operations Since 1 Count Value on IB1 [IB 1 Operations Since 1 Date] Parameter Number:

Page 246

Description of Features 4-5 1503-UM054C-EN-P – June 2013 Time. If the contactor did not close within 200mS then there is a major problem

Page 247

Parameters B-145 1503-UM054C-EN-P – June 2013 Operations Since 2 Count Value on IB1 [IB 1 Operations Since 2 Count Value] Parameter Numb

Page 248

B-146 Parameters 1503-UM054C-EN-P – June 2013 Time of Operations Since 2 Count Value on IB1 [IB 1 Operations Since 2 Time] Parameter Number:

Page 249 - B-74 Parameters

Parameters B-147 1503-UM054C-EN-P – June 2013 Date of Operations Since 0 Count Value on IB2 [IB 2 Operations Since 0 Date] Parameter Num

Page 250 - Parameters B-75

B-148 Parameters 1503-UM054C-EN-P – June 2013 Operations Since 1 Count Value on IB2 [IB 2 Operations Since 1 Count Value] Parameter Number:

Page 251 - B-76 Parameters

Parameters B-149 1503-UM054C-EN-P – June 2013 Time of Operations Since 1 Count Value on IB2 [IB 2 Operations Since 1 Time] Parameter Num

Page 252 - Parameters B-77

B-150 Parameters 1503-UM054C-EN-P – June 2013 Date of Operations Since 2 Count Value on IB2 [IB 2 Operations Since 2 Date] Parameter Number:

Page 253 - B-78 Parameters

Parameters B-151 1503-UM054C-EN-P – June 2013 Operations Since 0 Count Value on IB3 [IB 3 Operations Since 0 Count Value] Parameter Numb

Page 254 - Parameters B-79

B-152 Parameters 1503-UM054C-EN-P – June 2013 Time of Operations Since 0 Count Value on IB3 [IB 3 Operations Since 0 Time] Parameter Number:

Page 255 - B-80 Parameters

Parameters B-153 1503-UM054C-EN-P – June 2013 Date of Operations Since 1 Count Value on IB3 [IB 3 Operations Since 1 Date] Parameter Num

Page 256 - Parameters B-81

B-154 Parameters 1503-UM054C-EN-P – June 2013 Operations Since 2 Count Value on IB3 [IB 3 Operations Since 2 Count Value] Parameter Number:

Page 257 - B-82 Parameters

4-6 Description of Features 1503-UM054C-EN-P – June 2013 Delayed Restart (General) The contactors are assigned rated duties, which define ho

Page 258 - Parameters B-83

Parameters B-155 1503-UM054C-EN-P – June 2013 Time of Operations Since 2 Count Value on IB3 [IB 3 Operations Since 2 Time] Parameter Num

Page 259 - B-84 Parameters

B-156 Parameters 1503-UM054C-EN-P – June 2013 Date of Operations Since 0 Count Value on IB4 [IB 4 Operations Since 0 Date] Parameter Number:

Page 260 - Parameters B-85

Parameters B-157 1503-UM054C-EN-P – June 2013 Operations Since 1 Count Value on IB4 [IB 4 Operations Since 1 Count Value] Parameter Numb

Page 261 - B-86 Parameters

B-158 Parameters 1503-UM054C-EN-P – June 2013 Time of Operations Since 1 Count Value on IB4 [IB 4 Operations Since 1 Time] Parameter Number:

Page 262 - Parameters B-87

Parameters B-159 1503-UM054C-EN-P – June 2013 Date of Operations Since 2 Count Value on IB4 [IB 4 Operations Since 2 Date] Parameter Num

Page 263 - B-88 Parameters

B-160 Parameters 1503-UM054C-EN-P – June 2013 Operations Since 0 Count Value on IB5 [IB 5 Operations Since 0 Count Value] Parameter Number:

Page 264 - Parameters B-89

Parameters B-161 1503-UM054C-EN-P – June 2013 Time of Operations Since 0 Count Value on IB5 [IB 5 Operations Since 0 Time] Parameter Num

Page 265 - B-90 Parameters

B-162 Parameters 1503-UM054C-EN-P – June 2013 Date of Operations Since 1 Count Value on IB5 [IB 5 Operations Since 1 Date] Parameter Number:

Page 266 - Parameters B-91

Parameters B-163 1503-UM054C-EN-P – June 2013 Operations Since 2 Count Value on IB5 [IB 5 Operations Since 2 Count Value] Parameter Numb

Page 267 - B-92 Parameters

B-164 Parameters 1503-UM054C-EN-P – June 2013 Time of Operations Since 2 Count Value on IB5 [IB 5 Operations Since 1 Time] Parameter Number:

Page 268 - Parameters B-93

Description of Features 4-7 1503-UM054C-EN-P – June 2013  ‘IB3 Delay Restart Wait Time = ‘ ‘x Sec’ (Note: This value, as it is being v

Page 269 - B-94 Parameters

Parameters B-165 1503-UM054C-EN-P – June 2013 Length of Event Log on IB2 [IB 2 Event Present Length] Parameter Number: 319,262,205,148

Page 270 - Parameters B-95

B-166 Parameters 1503-UM054C-EN-P – June 2013 Length of Event Log on IB4 [IB 4 Event Present Length] Parameter Number: 321,264,_,_,_. Access

Page 271 - B-96 Parameters

Parameters B-167 1503-UM054C-EN-P – June 2013 Module Status of IB1 [IB Status] Parameter Number: 323,265,207,149,90. Access rule: Ge

Page 272 - Parameters B-97

B-168 Parameters 1503-UM054C-EN-P – June 2013 Invalid DeviceLogix Program Loaded [Invalid DeviceLogix Program] Parameter Number: 325,267,209

Page 273 - B-98 Parameters

Parameters B-169 1503-UM054C-EN-P – June 2013 Altitude Settings on MC Units Inconsistent [MC Altitude Set Warning] Parameter Number: 3

Page 274 - Parameters B-99

B-170 Parameters 1503-UM054C-EN-P – June 2013 Drop Out Time Source [Drop Out Time Source] Parameter Number: 329,271,213,155,96. Access rule:

Page 275 - B-100 Parameters

Parameters B-171 1503-UM054C-EN-P – June 2013 Contactor Coil Current for IB2 [IB 2 Contactor Coil Current] Parameter Number: 331,273,2

Page 276 - Parameters B-101

B-172 Parameters 1503-UM054C-EN-P – June 2013 Contactor Coil Current for IB4 [IB 4 Contactor Coil Current] Parameter Number: 333,275,_,_,_.

Page 277 - B-102 Parameters

Parameters B-173 1503-UM054C-EN-P – June 2013 Status Word for IB1 [IB 1 Status Word] Parameter Number: 335,276,217,158,98. Access rule:

Page 278 - Parameters B-103

B-174 Parameters 1503-UM054C-EN-P – June 2013 Status Word for IB2 [IB 2 Status Word] Parameter Number: 336,277,218,159,_. Access rule: Get

Page 279 - B-104 Parameters

4-8 Description of Features 1503-UM054C-EN-P – June 2013 Counters must be implemented to keep track of the Jog time as well as for the Jog Re

Page 280 - Parameters B-105

Parameters B-175 1503-UM054C-EN-P – June 2013 Status Word for IB3 [IB 3 Status Word] Parameter Number: 337,278,219,_,_. Access rule:

Page 281 - B-106 Parameters

B-176 Parameters 1503-UM054C-EN-P – June 2013 Status Word for IB4 [IB 4 Status Word] Parameter Number: 338,279,_,_,_. Access rule: Get Dat

Page 282 - Parameters B-107

Parameters B-177 1503-UM054C-EN-P – June 2013 Status Word for IB5 [IB 5 Status Word] Parameter Number: 339,_,_,_,_. Access rule: Get

Page 283 - B-108 Parameters

B-178 Parameters 1503-UM054C-EN-P – June 2013 Correct Termination Resistor Installed in MC System [Correct MC Termination Resistor] Parameter

Page 284 - Parameters B-109

Parameters B-179 1503-UM054C-EN-P – June 2013 Termination Resistor Installed in IB3 [IB3 Termination Resistor] Parameter Number: 342,2

Page 285 - B-110 Parameters

B-180 Parameters 1503-UM054C-EN-P – June 2013 Termination Resistor Installed in IB5 [IB5 Termination Resistor] Parameter Number: 344,_,_,_,_.

Page 286 - Parameters B-111

Parameters B-181 1503-UM054C-EN-P – June 2013 Status Word for the MC System [MC System Status] Parameter Number: 346,285,224,163,101.

Page 287 - B-112 Parameters

B-182 Parameters 1503-UM054C-EN-P – June 2013 MC System Ready Status [MC System Ready Status] Parameter Number: 347,286,225,164,102. Ac c es

Page 288

Parameters B-183 1503-UM054C-EN-P – June 2013 MC System Locked [MC System Locked] Parameter Number: 349,288,227,166,104. Access rule:

Page 289 - B-114 Parameters

B-184 Parameters 1503-UM054C-EN-P – June 2013 IB1 Firmware Version [IB1 Firmware Version] Parameter Number: 351,290,229,168,106. Access rule:

Page 290 - Parameters B-115

Description of Features 4-9 1503-UM054C-EN-P – June 2013 Items #30 to #49, in the Event Log, which apply to the DeviceLogix I/O, will on

Page 291 - B-116 Parameters

Parameters B-185 1503-UM054C-EN-P – June 2013 IB4 Firmware Version [IB4 Firmware Version] Parameter Number: 354,293,_,_,_. Access rule:

Page 292 - Parameters B-117

B-186 Parameters 1503-UM054C-EN-P – June 2013

Page 293 - B-118 Parameters

Appendix C 1503-UM054C-EN-P – June 2013 Maintenance Introduction The IntelliVAC Plus product has is a very robust device which contains only

Page 294 - Parameters B-119

C-2 Maintenance 1503-UM054C-EN-P – June 2013 I M P O R T A N TI M P O R T A N T The cause of the fuse failure should be identified before the fu

Page 295 - B-120 Parameters

Appendix D 1503-UM054C-EN-P – June 2013 Spare Parts Table D.1 – Spare Parts Item Description Part Number Internal Fuse 6.3A, 250V (Little

Page 296 - Parameters B-121

D-2 Spare Parts 1503-UM054C-EN-P – June 2013

Page 297 - B-122 Parameters

Appendix E 1503-UM054C-EN-P – June 2013 DeviceNet Information Identify Object Table E.1 - Class Attributes Attribute ID Access Rule Name Devi

Page 298

E-2 DeviceNet Information 1503-UM054C-EN-P – June 2013 Table E.3 – Device Status Bit No. Status Data Value Bit 0 Owned 0=not owned 1=owned

Page 299

DeviceNet Information E-3 1503-UM054C-EN-P – June 2013 Table E.6 – Instance Attributes Attribute ID Access Rule Name DeviceNet Data T

Page 300

E-4 DeviceNet Information 1503-UM054C-EN-P – June 2013 Explicit Connection Table E.9 - Instance Attributes (predefined slave explicit connection)

Page 301

4-10 Description of Features 1503-UM054C-EN-P – June 2013 Table 4.D – Event Log Data (cont.) Event Code Data Time Stamp OUTA Close 46 None “

Page 302

DeviceNet Information E-5 1503-UM054C-EN-P – June 2013 Parameter Object The parameter object and parameter object are all for mainly fo

Page 303 - B-128 Parameters

E-6 DeviceNet Information 1503-UM054C-EN-P – June 2013 Common Service Table E.12 - Service Codes Service Code Implementation for Service Name

Page 304 - Parameters B-129

DeviceNet Information E-7 1503-UM054C-EN-P – June 2013 Output (Consumed) Assembly and Layout Output assembly instances attribute and fo

Page 305

E-8 DeviceNet Information 1503-UM054C-EN-P – June 2013 Input (Produced) Assembly and Layout Table E.17 – Input assembly instances attribute and

Page 306

DeviceNet Information E-9 1503-UM054C-EN-P – June 2013 Important Notes: *About PNBnn/IBx-Outy: this is IntelliVAC ass embly’s unique f

Page 307

E-10 DeviceNet Information 1503-UM054C-EN-P – June 2013 Table E.22 – Instance Attributes Attribute ID Access Rule Attribute Name Data Type Defa

Page 308

DeviceNet Information E-11 1503-UM054C-EN-P – June 2013 Table E.22 – Instance Attributes (cont.) Attribute ID Access Rule Attribute Nam

Page 309

E-12 DeviceNet Information 1503-UM054C-EN-P – June 2013 Table E.25 - Instance Attribute Parameter No. Control Parameter Access Rule Type Descripti

Page 310 - Parameters B-135

DeviceNet Information E-13 1503-UM054C-EN-P – June 2013 Table E.25 - Instance Attribute (cont.) Parameter No. Control Parameter Access Ru

Page 311 - B-136 Parameters

E-14 DeviceNet Information 1503-UM054C-EN-P – June 2013 Table E.25 - Instance Attribute (cont.) Parameter No. Control Parameter Access Rule Type

Page 312 - Parameters B-137

Description of Features 4-11 1503-UM054C-EN-P – June 2013 Coil Currents The coil currents represent the average value of the particular

Page 313 - B-138 Parameters

DeviceNet Information E-15 1503-UM054C-EN-P – June 2013 PCP Object (Motor Control Center Object) Class Attributes: None Number of Insta

Page 314 - Parameters B-139

E-16 DeviceNet Information 1503-UM054C-EN-P – June 2013 Data Table Layout Table E.29 shows the data table layout. Table E.29 – DeviceLogix Data

Page 315 - B-140 Parameters

DeviceNet Information E-17 1503-UM054C-EN-P – June 2013 Table E.29 – DeviceLogix Data Table Layout (cont.) Byte Bit 7 Bit 6 Bit 5 B

Page 316 - Parameters B-141

E-18 DeviceNet Information 1503-UM054C-EN-P – June 2013

Page 317 - B-142 Parameters

Appendix F 1503-UM054C-EN-P – June 2013 IntelliVAC Plus Firmware Introduction In order to update the firmware of the IntelliVAC Plus module

Page 318 - Parameters B-143

F-2 IntelliVAC Plus Firmware 1503-UM054C-EN-P – June 2013 • Configure the selected DeviceNet driver Figure F.2 – DeviceNet Drive Configura

Page 320 - Parameters B-145

Medium Voltage Products, 135 Dundas Street, Cambridge, ON, N1R 5X1 Canada, Tel: (1) 519.740.4100, Fax: (1)

Page 321 - B-146 Parameters

4-12 Description of Features 1503-UM054C-EN-P – June 2013 Open Coil Test To check that there is a coil(s) connected to the IntelliVAC Plus

Page 322 - Parameters B-147

ii Table of Contents 1503-UM054C-EN-P – June 2013 Chapter 4 Description of Features (cont.) Supply Voltages ...

Page 323 - B-148 Parameters

Description of Features 4-13 1503-UM054C-EN-P – June 2013 Supply Voltages The AC and DC supply voltage measurements represent the RMS

Page 324 - Parameters B-149

4-14 Description of Features 1503-UM054C-EN-P – June 2013 The ‘I Bx Line Undervoltage’ and ‘I Bx Line Undervoltage’ values are included to a

Page 325 - B-150 Parameters

Description of Features 4-15 1503-UM054C-EN-P – June 2013 Time Zone Selection To facilitate in the setting of the time of day for diffe

Page 326 - Parameters B-151

4-16 Description of Features 1503-UM054C-EN-P – June 2013 The IntelliVAC Plus is adaptable to a range of atmospheric pressures and altitudes

Page 327 - B-152 Parameters

Description of Features 4-17 1503-UM054C-EN-P – June 2013 “Master” Counter The Master c ounter w ill inc lude all operations, since

Page 328 - Parameters B-153

4-18 Description of Features 1503-UM054C-EN-P – June 2013  ‘I B2 Reset Ops Since Counter’ (present ‘IB2 Ops Since 0 data/time’ saved to ‘IB2

Page 329 - B-154 Parameters

Description of Features 4-19 1503-UM054C-EN-P – June 2013  ‘IB3 Operation Since 0 Count Value =’ ‘0’ to ‘16777215’ 24 bit counter)  ‘

Page 330 - Parameters B-155

4-20 Description of Features 1503-UM054C-EN-P – June 2013 “Average Operations” Counter The Average Operations counter will include Average

Page 331 - B-156 Parameters

Description of Features 4-21 1503-UM054C-EN-P – June 2013 Configuration The IntelliVAC Plus Unit will be configured in one of two

Page 332 - Parameters B-157

4-22 Description of Features 1503-UM054C-EN-P – June 2013 In an MC system all MC operation will cease and communications between the various

Page 333 - B-158 Parameters

Table of Contents iii 1503-UM054C-EN-P – June 2013 Chapter 4 Description of Features (cont.) Network Status (DeviceNet)...

Page 334 - Parameters B-159

Description of Features 4-23 1503-UM054C-EN-P – June 2013 Table 4.E – IB Fault/Warning Descriptions IntelliVAC Status Indication (Series

Page 335 - B-160 Parameters

4-24 Description of Features 1503-UM054C-EN-P – June 2013 The Contactor status LED is off to indicate that the contactor is in an Open condit

Page 336 - Parameters B-161

Description of Features 4-25 1503-UM054C-EN-P – June 2013 Close, Jog or Trip commands are present during a power on sequence.

Page 337 - B-162 Parameters

4-26 Description of Features 1503-UM054C-EN-P – June 2013 Note: Close and Jog are for an Electrically Held contactor and Close and Trip are

Page 338 - Parameters B-163

Description of Features 4-27 1503-UM054C-EN-P – June 2013 This is a Fault condition and the IntelliVAC Plus will not respond to other

Page 339 - B-164 Parameters

4-28 Description of Features 1503-UM054C-EN-P – June 2013 Contactor Drop Out During Hold This is a Warning condition and the status of the c

Page 340 - Parameters B-165

Description of Features 4-29 1503-UM054C-EN-P – June 2013 Microcontroller Malfunction This is a serious Fault condition and the Intelli

Page 341 - B-166 Parameters

4-30 Description of Features 1503-UM054C-EN-P – June 2013 Contactor Fails to Drop Out This is a Fault condition and the IntelliVAC Plus wil

Page 342

Description of Features 4-31 1503-UM054C-EN-P – June 2013 The Contactor status LED is off to indicate that the contactor is in an Open c

Page 343 - B-168 Parameters

4-32 Description of Features 1503-UM054C-EN-P – June 2013 This condition is valid for both Electrically Held and Mechanically Latched conta

Page 344 - Parameters B-169

iv Table of Contents 1503-UM054C-EN-P – June 2013 Chapter 6 Wiring Wiring (MC) ...

Page 345 - B-170 Parameters

Description of Features 4-33 1503-UM054C-EN-P – June 2013 Table 4.F - Plus Fault/Warning Description Fault/Warning Red LED Green LED

Page 346 - Parameters B-171

4-34 Description of Features 1503-UM054C-EN-P – June 2013 When a fault/warning occurs, the appropriate LED will flash and the appropriate fau

Page 347 - B-172 Parameters

Description of Features 4-35 1503-UM054C-EN-P – June 2013 Programming Base Unit(s) This is a Normal firmware flashing condition and no

Page 348

4-36 Description of Features 1503-UM054C-EN-P – June 2013 Line Undervoltage This is a Warning condition which may not be rectified by the us

Page 349

Description of Features 4-37 1503-UM054C-EN-P – June 2013 Table 4.G – Contactor Extended Close Times CONTACTOR CONFIGURATION @ Vinput Ma

Page 350

4-38 Description of Features 1503-UM054C-EN-P – June 2013 MC Altitude Setting Warning This is a Warning condition which indicates that the

Page 351

Description of Features 4-39 1503-UM054C-EN-P – June 2013 Application Programming Error – CRC This is a Fault c ondition which indica

Page 352

4-40 Description of Features 1503-UM054C-EN-P – June 2013 There is a Red/Green bi-c olor LED which is used to indicate the DeviceNet network

Page 353 - B-178 Parameters

Description of Features 4-41 1503-UM054C-EN-P – June 2013 IE Determining Network Baud Rate The DeviceNet status LED is flashing Green.

Page 354 - Parameters B-179

4-42 Description of Features 1503-UM054C-EN-P – June 2013 Table 4.I – DeviceNet Module Status LED Fault/Warning Red LED Green LED Descript

Page 355

Table of Contents v 1503-UM054C-EN-P – June 2013 Chapter 8 Configurations (cont.) MC RS485 Addressing ...

Page 356

Description of Features 4-43 1503-UM054C-EN-P – June 2013 The DeviceNet status LED is solid Green.

Page 357 - B-182 Parameters

4-44 Description of Features 1503-UM054C-EN-P – June 2013 Recoverable Fault This is a Warning condition and indicates that the IntelliVAC P

Page 358

Description of Features 4-45 1503-UM054C-EN-P – June 2013 For the 7-segment LED display, the ‘Watchdog Timeout’ and the ‘System Lock-Out

Page 359 - B-184 Parameters

4-46 Description of Features 1503-UM054C-EN-P – June 2013 MC Bad MC #1 This is a Fault condition and indicates that the IntelliVAC MC #1, wh

Page 360 - Parameters B-185

Description of Features 4-47 1503-UM054C-EN-P – June 2013 See Table 8.K for a definition of w hic h IntelliVAC unit is to have the term

Page 361 - B-186 Parameters

4-48 Description of Features 1503-UM054C-EN-P – June 2013 The 7-segment display will display the flashing character ‘7’ + ‘Dec imal Point’.

Page 362 - Maintenance

Chapter 5 1503-UM054C-EN-P – June 2013 IntelliVAC Plus Basic Wiring Fuse Protection The IntelliVAC module requires external fuse protection

Page 363 - Battery Holder

5-2 IntelliVAC Plus Basic Wiring 1503-UM054C-EN-P – June 2013 Grounding The IntelliVAC module must be connected to a common ground terminal

Page 364 - Spare Parts

IntelliVAC Plus Basic Wiring 5-3 1503-UM054C-EN-P – June 2013 Interface Connections Further control interface connections are made at a

Page 365 - D-2 Spare Parts

5-4 IntelliVAC Plus Basic Wiring 1503-UM054C-EN-P – June 2013 When configured for basic control the IntelliVAC Plus can be applied with t

Page 366 - DeviceNet Information

vi Table of Contents 1503-UM054C-EN-P – June 2013 Chapter 9 DeviceLogix (cont.) Up Down Counter...

Page 367 - DeviceNet Object

IntelliVAC Plus Basic Wiring 5-5 1503-UM054C-EN-P – June 2013 A T T E N T I O NA T T E N T I O N For Emergency Stop applications requiri

Page 368

5-6 IntelliVAC Plus Basic Wiring 1503-UM054C-EN-P – June 2013 MOV321EC-+4TCO1211AUX CCO56L1 L2/NG+ -STOPSTARTOVERLOADCONTROLPOWERFUSE*M-IV9 1

Page 369 - Explicit Connection

IntelliVAC Plus Basic Wiring 5-7 1503-UM054C-EN-P – June 2013 IntelliVAC control may be used for mechanical latch contactors. A mome

Page 370 - Parameter Object

5-8 IntelliVAC Plus Basic Wiring 1503-UM054C-EN-P – June 2013 Capacitor Trip The IntelliVAC can be configured to provide capacitor trip

Page 371 - Common Service

IntelliVAC Plus Basic Wiring 5-9 1503-UM054C-EN-P – June 2013 MOV321EC-+4TCO1211AUX CCO56L1 L2/NG+ -CLOSEOVERLOADCONTROLPOWERFUSE*CONTR

Page 372 - IB OutB=open coil command

5-10 IntelliVAC Plus Basic Wiring 1503-UM054C-EN-P – June 2013 Table 5.D – Maximum TDUV Time (without Capacitor) Control Voltage Max. TD

Page 373 - 1503-UM054C-EN-P – June 2013

IntelliVAC Plus Basic Wiring 5-11 1503-UM054C-EN-P – June 2013 Figure 5.9 – Wiring Diagram for

Page 374 - DNI (IE) Object

5-12 IntelliVAC Plus Basic Wiring 1503-UM054C-EN-P – June 2013 Figure 5.10 – Wiring Diagram for Full Voltage Non-Reversing Logic M

Page 375

Chapter 6 1503-UM054C-EN-P – June 2013 Wiring Wiring (MC) Pre Configured Logic Mode The IntelliVAC Plus comes with five

Page 376

6-2 Wiring (MC) 1503-UM054C-EN-P – June 2013 Wiring (MC) (cont.) After selecting the desired control program, the IntelliVAC Plus module mu

Page 377

Table of Contents vii 1503-UM054C-EN-P – June 2013 Appendix D Spare Parts ...

Page 378

Wiring (MC) 6-3 1503-UM054C-EN-P – June 2013 Figure 6.2 – Wiring Diagram for Full Voltage Reversing Configuration Required: • Gate

Page 379 - Table E.26 - Common Services

6-4 Wiring (MC) 1503-UM054C-EN-P – June 2013 Figure 6.3 – Wiring Diagram for SMC This circuit is set up for Soft Start or Current Limit

Page 380 - Number of Instances: 1

Wiring (MC) 6-5 1503-UM054C-EN-P – June 2013 Figure 6.4 – Wiring Diagram for SMC (cont.) Configuration Required: None This ci

Page 381 - Data Table Layout

6-6 Wiring (MC) 1503-UM054C-EN-P – June 2013 Figure 6.5 – Wiring Diagram for SMC with PFCC This circuit is set up for Soft Start or Curr

Page 382

Wiring (MC) 6-7 1503-UM054C-EN-P – June 2013 Figure 6.6 – Wiring Diagram for SMC with PFCC (cont.) Configuration Required: None

Page 383 - E-18 DeviceNet Information

6-8 Wiring (MC) 1503-UM054C-EN-P – June 2013 Figure 6.7 – Wiring Diagram for Reduced Voltage Reactor RVR Configuration Required: • Gate 2

Page 384 - IntelliVAC Plus Firmware

Wiring (MC) 6-9 1503-UM054C-EN-P – June 2013 Incomplete Sequence Timer The Incomplete sequence timer is designed to ensure that the du

Page 385

6-10 Wiring (MC) 1503-UM054C-EN-P – June 2013 Figure 6.8 – Wiring Diagram for Reduced Voltage Auto Transformer RVAT Configuration Requir

Page 386

Wiring (MC) 6-11 1503-UM054C-EN-P – June 2013 Incomplete Sequence Timer The Incomplete sequence timer is designed to ensure that the d

Page 387 - Medium Voltage Products

6-12 Wiring (MC) 1503-UM054C-EN-P – June 2013