Bulletin 1500/1900 Isolation Switch Handle – Interlock Mechanism Replacement 13
1500-IN052C-EN-P – January 2007
Procedure for Operating Lever Replacement – STEP 8
Connecting Rod
Retrofit Operating Lever
Hitch Pin
Clevis Pin
Connecting Rod
Clevis Pin
Hitch Pin
Washer
800 Amp
For regular 400AMP and 600AMP:
1) Insert the Clevis Pin into the top hole of the Retrot Starter Operating Lever
2) Insert the Hitch Pin into the Clevis Pin
For 800AMP:
1) Insert the Clevis Pin through Connecting Rod clevis holes and the top hole of the Retrot Operating
Lever at the same time keep the Washers in position
2) Insert the Hitch Pin into the Clevis Pin