Rockwell-automation 150 USE MN/SMC DIALOG + CONTROLLER Manuel d'utilisateur Page 173

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 189
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 172
B-4
Parameter Information
Table B.1 (cont.) Parameter List
Read-only capability.
The scale factor is 100 when Motor FLC, parameter 70, has a programmed value of up to 10.0 Amps; above 10.0 Amps, the scale factor is 10.
Group
Parameter
Description
Parameter
Number
Display
Units
Scale
Factor
Minimum Maximum
Default
Setting
User
Setting
Calibrate
Overload
Class
36 Off, 10, 15, 20, and 30 Off
Overload
Reset
88 Manual-Auto Manual
Motor HP
Rating
79 HP 10 0.0 6,553.5 0.0
Motor kW
Rating
80 kW 10 0.0 6,553.5 0.0
Line Voltage 69 Volts 1 0 9999 480
Motor FLC 70 Amps 10 1.0 999.9 1.0
Service
Factor
84 100 0.01 1.99 1.15
Motor Code
Letter
72
A, B, C, D, E, F, G, H, J, K, L,
M, N, P, R, S, T, U, and V
G
LRC Ratio 81 10 0.0 19.9 0.0
Converter
Rating
74 None, 20, 180, 630 None
CT Ratio 75
5, 50, 75, 100, 150, 200,
250, 300, 400, 500, 600, 750,
800, 1000, 1200 :5
5:5
Calibration 76 Off, Activate Off
Enter Calib.
Amps
77 Amps
0.01 999.9 0.0
Current
Phase A
4Amps10
Parameter
Mgmt.
17
Ready, Default Init.
Recll Frm EE,Store In EE
Ready