EN916 - Variable Voltage Control 3
Voltage Control
[Volt Trim% Ref]
This parameterspecifies thevoltagecommandtrim% val-
ue added/subtractedto [Volt Preset] when[Volt Select] is
set to “Pre+TrimRef”. The trim value is
±Volt Trim% of
[Rated Voltage].
Minimum Input = –Volt Trim% Value
Mid-Point Input = No Trim
Maximum Input = +Volt Trim% Value
The parameter value is cleared at power-up and is not
retainedineepromstorage. Thisparameterisintendedto
beusedwithaSCANportcommunicationsadapterviathe
[Data In xx] Adapter I/O parameters.
Parameter Number 341
Parameter Type Read and Write
Display Units / Drive Units 1% / 4096 = 100%
Factory Default 0%
Minimum Value 0%
Maximum Value +100%
Vue de la page 2